BIS Menu  |  Property Permits  |  ECB Violations  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M367377
Premises: 1120 5 AVENUE MANHATTAN BIN: 1047101     Block: 1505   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1120 5 AV Census Tract:   160.01 Health Area:  2820
5TH AVE/ PENTHOUSE A Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   EAST 93 STREET,    EAST 94 STREET
Status:   C - JOB IS SIGNED OFF 04/22/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/13/2015 9:49 AM
Application Entered:   05/13/2015 Job Start Date:   05/15/2015
Last Change:   04/22/2017 Job End Date:   12/01/2015
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     04/06/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012435 Licensee Name: FRANK V CARUSO
Firm: 004389 Firm Name: FVC ELECTRIC, INC
Firm Phone: 347-506-3990  Firm Address: 61-43 186TH STREET, SUITE 521 FRESH MEADOWS NY 11365 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $96.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT BERGMAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
PEN  65  70    35  65             
Buildings Total 65  70    35  65                
Total Units : 235 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/08/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M367377
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/08/2017 03/08/2017 PHG V (60) (5)
INSPECTION COMMENTS: CONTRACTOR TO FILE FOR PANEL FEEDER A/C HEATER ECT
 
(2) 04/06/2017 04/10/2017 MLF C R (45) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M367377
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(PENTHOUSE) BOTH A/C UNITS OVER FUSED 240.3
RSLV 03/08/2017 03/08/2017 04/06/2017
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(PENTHOUSE) NO GFCI IN LAUNDRY RM
RSLV 03/08/2017 03/08/2017 04/06/2017
 
003 (999) OTHER
(PENTHOUSE) ALL BATH RM CKT ON 15 AMP LINES 210.11
RSLV 03/08/2017 03/08/2017 04/06/2017
 
004 (999) OTHER
(PENTHOUSE) BURIED DRIVER IN KITCHEN 410.144
RSLV 03/08/2017 03/08/2017 04/06/2017
 
005 (999) OTHER
(PENTHOUSE) PANEL ,LOCATED ON STEPS 240.24
RSLV 03/08/2017 03/08/2017 04/06/2017