BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M367332
Premises: 355 GREENWICH STREET MANHATTAN BIN: 1002083     Block: 181   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 355 GREENWICH ST Census Tract:   39 Health Area:  7700
2 Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   HARRISON STREET,    FRANKLIN STREET
Status:   C - JOB IS SIGNED OFF 11/10/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/12/2015 7:35 PM
Application Entered:   05/12/2015 Job Start Date:   05/12/2015
Last Change:   11/10/2016 Job End Date:   05/12/2016
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     11/03/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012413 Licensee Name: JOSEPH P INCANTALUPO
Firm: 004204 Firm Name: PINPOINT ELECTRIC CORP
Firm Phone: 718-784-0571  Firm Address: 10-32 47TH ROAD LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LOU RAMIERZ
Owner Business Name: KAYSER BAKERY
Authorized Representative:  ELEVATOR SUPERIOR
Relationship To Owner:   DOB ADMINISTRATOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/19/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M367332
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/19/2016 10/19/2016 STP V (30) (2)
INSPECTION COMMENTS: FAIL
 
(2) 11/03/2016 11/04/2016 STP C R (30) (0)
INSPECTION COMMENTS: PASS OBJECTIONS NOT SHOWING ON ACCELLA CONTACTED OFFICE. CONTRACTOR HAD PROOF FUSES WHERE GOOD BASED ON MANUFACTURE SPECS.

OBJECTION FOR APPLICATION #: M367332
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) BOTH DISCONNECTS NEUTRAL BONDED 250.24
RSLV 10/19/2016 10/19/2016 11/03/2016
 
002 (999) OTHER
(BASEMENT) MOTOR OVERFUSED BASED OFF NAMEPLATE 430.52
RSLV 10/19/2016 10/19/2016 11/03/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order