BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M367139
Premises: 1349 2 AVENUE MANHATTAN BIN: 1043944     Block: 1426   Lot: 21
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1349 SECOND AV Census Tract:   126 Health Area:  4200
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
Related Job Number:    122359893
DOB Cross Street(s):   EAST 71 STREET,    EAST 72 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/08/2015 6:30 AM
Application Entered:   05/08/2015 Job Start Date:   05/08/2015
Last Change:   08/22/2025 Job End Date:   11/08/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     09/09/2015      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 010346 Licensee Name: PHILIP A ROBINSON
Firm: 001157 Firm Name: PHILIP A. ROBINSON
Firm Phone: 718-783-6542  Firm Address: 43-49 10TH STREET.SUITE 107 LONG ISLAND CITY NY 11101-6999 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $180.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   SHOWROON
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ZAHEER AKBER
Owner Business Name: MANHATTAN CABINETS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  2/0 THHN
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  42 CKTS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  GND  50  60  15  50  14         
Buildings Total 50  60  15  50     14           
Total Units : 191 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/15/2015
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M367139
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/09/2015 09/15/2015 BUR A (45) (6) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M367139
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
GROUND: BOX SET BACK MORE THAN 1/4" NOT FLUSH COMBUSTIBLE.. 314.20
OPEN 09/09/2015 09/09/2015
 
002 (999) OTHER
GROUND: DOUBLE LUGGING ON A.C DISCONNECTS T-OUT.. 110.14
OPEN 09/09/2015 09/09/2015
 
003 (999) OTHER
OUTSIDE: NO G.F.I.PROVIDED A.C.EQUIPMENT.. 210.63
OPEN 09/09/2015 09/09/2015
 
004 (999) OTHER
OUTSIDE: NO PIPE SUPPORT FOR I.M.C.. 342.30
OPEN 09/09/2015 09/09/2015
 
005 (999) OTHER
GROUND: A.C.UNITS ARE OVERFUSED MANUFACTURED SPEC.. 110.3
OPEN 09/09/2015 09/09/2015
 
006 (999) OTHER
BASEMENT: DEFECTIVE WIRING IN USE FOR LIGHT FIXTURES.. 110.2A
OPEN 09/09/2015 09/09/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order