BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M367087
Premises: 57 GREENE STREET MANHATTAN BIN: 1007297     Block: 486   Lot: 7503
   
Application Completed and Certified

Filed: 57 GREENE ST Census Tract:   49 Health Area:  6800
1ST FLOOR,CELLAR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   JEFFREY RUDES
DOB Cross Street(s):   BROOME STREET,    SPRING STREET
Status:   C - JOB IS SIGNED OFF 11/25/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/07/2015 12:24 PM
Application Entered:   05/07/2015 Job Start Date:   05/07/2015
Last Change:   11/25/2015 Job End Date:   08/01/2015
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     11/20/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009808 Licensee Name: PETER BLAKE
Firm: 000238 Firm Name: BLAKE ELEC. CONTR. CO., I
Firm Phone: 718-292-8080  Firm Address: 311 EAST 150TH STREET BRONX NY 10451 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $168.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122269133
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: UZI B ABRAHAM
Owner Business Name: MANAGING MEMBER
Authorized Representative:  UZI ABRAHAM
Relationship To Owner:   MANAGING MEMBER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  3PH,100A,42CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    85  20         
001    85  20      30         
Buildings Total 170  40    14       35         
Total Units : 262 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/03/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M367087
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/31/2015 09/03/2015 BUR V (60) (4) Y
INSPECTION COMMENTS: LIGHTING PANEL NOT INSPECTED
 
(2) 11/20/2015 11/25/2015 PHG C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M367087
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
OTHER RECEPTACLES ON GND AND BASEMENT FLOOR RECESSED MILLWORKCOMBUSTIBLE MATERIAL 314.20
RSLV 08/31/2015 08/31/2015 11/20/2015
 
002 (999) OTHER
OTHER RECEPTACLES LOOSE ON WALL NOT SECURED PROPERLY THROUGH OUT406.4
RSLV 08/31/2015 08/31/2015 11/20/2015
 
003 (999) OTHER
PANEL MULTI-WIRE CKT HAS NO SIMULTANEOUSLY DISCONNECT MEANS. 210.4
RSLV 08/31/2015 08/31/2015 11/20/2015
 
004 (999) OTHER
BASEMENT EXTENSION CORD USE AS PERMANENT WIRING FOR WORK STATION400.8
RSLV 08/31/2015 08/31/2015 11/20/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.