BIS Menu  |  ECB Query for LL 158/17 Pro Cert Restriction  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M366630
Premises: 14 EXCHANGE PLACE MANHATTAN BIN: 1000830     Block: 27   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 20 EXCHANGE PL Census Tract:   7 Health Area:  7700
14 / 15 Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10005 Community Board:   101
DOB Cross Street(s):   HANOVER STREET,    WILLIAM STREET
Status:   C - JOB IS SIGNED OFF 12/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/28/2015 8:00 AM
Application Entered:   04/28/2015 Job Start Date:   04/28/2015
Last Change:   12/14/2017 Job End Date:   05/05/2015
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     10/23/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011451 Licensee Name: ROBERT E SALINGER
Firm: 003205 Firm Name: JOROB CONTR'G & ELEC'L CO
Firm Phone: 212-704-2040  Firm Address: 1040 AVENUE OF THE AMERICAS INC. NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $2,554.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: RBNB 20 OWNER LLC
Authorized Representative:  RICHARD RAMOS
Relationship To Owner:   REPRESENTITIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  60  24 CIRCUIT - 100 AMP
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
014    500  30  60                 
015    400  28  50                 
Buildings Total 900  58  110                    
Total Units : 1068 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 08/15/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M366630
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/10/2015 06/17/2015 EID A (105) (6) Y
INSPECTION COMMENTS: 1422,1419,1416,1417,1411,1515,1521
 
(2) 08/14/2017 08/15/2017 CLC H X (45) (0) Y
INSPECTION COMMENTS: OBJECTION REMAIN
 
(3) 10/23/2017 10/23/2017 EDB C R (45) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M366630
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) 14/15: PNLS MISSING DIRECTORIES T-OUT.. 408.4
RSLV 06/10/2015 06/10/2015 10/23/2017
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) LAUNDRY RM: RECEP NOT G.F.C.I.PROTECTED.. 210.8
RSLV 06/10/2015 06/10/2015 10/23/2017
 
003 (999) OTHER
(ALL FLOORS)KITCHEN: RECEPT SET BACK IN COMBUSTIBLE(COUNTER AND MICRO).. 314.20
RSLV 06/10/2015 06/10/2015 10/23/2017
 
004 (999) OTHER
(ALL FLOORS) 14/15: HALLWAY RECEP SET BACK TOO DEEP.. 314.20
RSLV 06/10/2015 06/10/2015 10/23/2017
 
005 (999) OTHER
(ALL FLOORS) 14/15: OVEN OVERFUSED AS PER MAN SPEC.. 110.3
RSLV 06/10/2015 06/10/2015 10/23/2017
 
006 (999) OTHER
(ALL FLOORS) MECH.RM: 15FL NO MEANS OF DISC FOR HEATERS.. 424.19
RSLV 06/10/2015 06/10/2015 10/23/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  ECB Query for LL 158/17 Pro Cert Restriction  |  Electrical Inspection Work Order  |  Back