Premises: 59 JANE STREET MANHATTAN BIN: 1011645     Block: 626   Lot: 12
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 61 JANE ST Census Tract:   79 Health Area:  6100
THIRD FLOOR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   HUDSON STREET,    GREENWICH STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 04/27/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/27/2015 11:14 AM
Application Entered:   04/27/2015 Job Start Date:   04/27/2015
Last Change:   04/27/2016 Job End Date:   12/31/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     04/26/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010985 Licensee Name: LINDEN J TUDOR
Firm: 002700 Firm Name: LINTECH ELECTRIC, INC
Firm Phone: 718-941-3766  Firm Address: 3006 TILDEN AVENUE BROOKLYN NY 11226 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $65.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARY LAMAS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  1 SET OF 24 CKT SINGLE PH
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3G  14  13    25               
Buildings Total 14  13    25                  
Total Units : 52 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 04/27/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M366590
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/12/2015 11/19/2015 TOR Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 04/26/2016 04/27/2016 EDB V (45) (5)
INSPECTION COMMENTS: P

OBJECTION FOR APPLICATION #: M366590
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 003) PANEL AND SPLICE BOX.
OPEN 04/26/2016 04/26/2016
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 003) OVER 10 CURRENT CONDUCTOR IN RACEWAY TO PANEL
OPEN 04/26/2016 04/26/2016
 
003 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 003) MC CABLE : T-OUT
OPEN 04/26/2016 04/26/2016
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 003) PANEL AND SPLICE BOX : SHEETROCK SCREW FOR GND 250.8
OPEN 04/26/2016 04/26/2016
 
005 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(FLOOR: 003) KITCHEN PENINSULA : MISSING RECEPTACLE
OPEN 04/26/2016 04/26/2016