BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M366214
Premises: 418 EAST 82 STREET MANHATTAN BIN: 1050398     Block: 1561   Lot: 34
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 420 E 82 ST Census Tract:   136 Health Area:  3800
BSMT/ ROOF Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):    1 AVENUE,    YORK AVENUE
Status:   C - JOB IS SIGNED OFF 07/13/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/16/2015 8:38 AM
Application Entered:   04/16/2015 Job Start Date:   04/16/2015
Last Change:   07/13/2016 Job End Date:   06/25/2015
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     07/12/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012074 Licensee Name: RAVI MANGROO
Firm: 003771 Firm Name: GUIDING LIGHT ELECTRIC IN
Firm Phone: 718-847-5700  Firm Address: 125-18 101ST AVENUE, 1FL S. RICHMOND.HILL,QUEENS NY 11419 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $173.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES MARSHALL
Owner Business Name: MARFAM REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100 A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  1 ELEVATOR
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  ELEV               
Buildings Total                 
Total Units : 12 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/10/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ELEVATOR MOTOR ROOM AND CAR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M366214
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/08/2016 06/10/2016 BUR V (35) (4)
INSPECTION COMMENTS: ELEVATOR ID 1P24930
 
(2) 07/12/2016 07/13/2016 MLF C R (30) (0)
INSPECTION COMMENTS: ALL OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M366214
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR) GFCI RECEPTACLE NOT WIRED PROPERLY IN PIT
RSLV 06/08/2016 06/08/2016 07/12/2016
 
002 (999) OTHER
(ROOF) EMT FROM MOTOR TO CONTROLLER NOT PROPERLY GROUNDED
RSLV 06/08/2016 06/08/2016 07/12/2016
 
003 (999) OTHER
(ROOF) PASSENGER DISCONNECT FUSE NOT SIZED PROPERLY
RSLV 06/08/2016 06/08/2016 07/12/2016
 
004 (999) OTHER
(ROOF) ARC FLASH STICKER NOT PROVIDED ON EQUIPMENT
RSLV 06/08/2016 06/08/2016 07/12/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.