BIS Menu  |  Bldg Info Search  |  Comments  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M366213
Premises: 954 1 AVENUE MANHATTAN BIN: 1040157     Block: 1364   Lot: 47
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 956 1 AV Census Tract:   86.03 Health Area:  5000
CELLAR, 1/FL Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   106
DOB Cross Street(s):   EAST 52 STREET,    EAST 53 STREET
Status:   C - JOB IS SIGNED OFF 02/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/16/2015 7:42 AM
Application Entered:   04/16/2015 Job Start Date:   04/16/2015
Last Change:   02/14/2017 Job End Date:   04/20/2015
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     02/14/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $70.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   LAUNDROMAT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLIAM GOTTLIEB
Owner Business Name: 400 EAST 53RD STREET LLC
Authorized Representative:  WILLIAM GOTTLIEB
Relationship To Owner:   SELF


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 01/24/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M366213
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/13/2015 07/16/2015 EDB A (50) (10) Y
INSPECTION COMMENTS: NONE
 
(2) 10/31/2016 11/01/2016 MLF J Y (31) (0)
INSPECTION COMMENTS: SOME OBJECTIONS STILL EXIST
 
(3) 01/06/2017 01/09/2017 PHG J Y (25) (0)
INSPECTION COMMENTS: NO WORKING SPACE AT TIME OF INSPECTION STORAGE IN FRONT OF ALL ELECTRICAL EQUIPMENT IN BSMT
 
(4) 01/23/2017 01/24/2017 MQY H X (17) (0) Y
INSPECTION COMMENTS: NO PROGRESS
 
(5) 02/14/2017 02/14/2017 GYM C R (45) (0)
INSPECTION COMMENTS: OBJECTION REMOVED.

OBJECTION FOR APPLICATION #: M366213
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(ALL FLOORS)T-OUT MC CABLE NOT PROPERLY TERMINATED AT SPLICE BOX(S) 330.40
RSLV 07/13/2015 07/13/2015 10/31/2016
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) T-OUT EQUIPMENT NOT PROPERLY GND 250.112,118
RSLV 07/13/2015 07/13/2015 10/31/2016
 
003 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(ALL FLOORS) CELLING LIGHT FIXTURE NOT PROPERLY SECURED 410.30,36
RSLV 07/13/2015 07/13/2015 10/31/2016
 
004 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(ALL FLOORS)CELLING FLEX CORD USED FOR PERMANENT WIRING OF LIGHT FIXTURE 400.8
RSLV 07/13/2015 07/13/2015 01/06/2017
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ALL FLOORS) BASEMENT 100 A S.S NOT PROPERLY GND 250.24C
RSLV 07/13/2015 07/13/2015 10/31/2016
 
006 (133) NO GROUND ROD: BASEMENT OR OUTSIDE
(ALL FLOORS) BASEMENT NO GND ROD PROVIDED FOR S.SW 250.52
RSLV 07/13/2015 07/13/2015 10/31/2016
 
007 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(ALL FLOORS) BASEMENT NO WORKING SPARE FOR SERVICE EQUIPMENT 110.26
RSLV 07/13/2015 07/13/2015 02/14/2017
 
008 (999) OTHER
(ALL FLOORS) T-OUT NO ARC FLASH WARNING FOR NEW EQUIPMENT 110.16
RSLV 07/13/2015 07/13/2015 10/31/2016
 
009 ( 30) OUTLET BOXES ARE NOT SECURED
(ALL FLOORS) CELLING OUTLET BOX(S) NOT SECURED 314.23
RSLV 07/13/2015 07/13/2015 01/06/2017
 
010 (999) OTHER
(ALL FLOORS) 1 FLOOR TOP OF PANEL SPLICE BOX OVERFILL T 314.16A
RSLV 07/13/2015 07/13/2015 10/31/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Bldg Info Search  |  Comments  |  Back