| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
30A |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
600A |
| D. 601 Up to 1200 AMPS |
2 |
1-800A; 1-1200A |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
5 |
|
| B. Over #2 to 1/0 |
37 |
|
| C. Over 1/0 to 250 MCM |
3 |
|
| D. Over 250 MCM |
6 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
38 |
|
| C. 3 Phase Up to 225 AMPS |
8 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 002) RECEPTACLES ON DECK NOT WR. |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 002 |
(999) |
OTHER (FLOOR: 002) GREEN WIRES NOT TERMINATED IN JUNCTION BOXES. 250. |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 003 |
(284) |
NO OUTLET FOR KITCHEN ISLAND (FLOOR: 012) NO RECEPTACLE PROVIDED KITCHEN ISLAND IN 12(B). |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 004 |
( 30) |
OUTLET BOXES ARE NOT SECURED (FLOOR: 012) SPLICE BOXES NOT SUPPORTED IN CEILING BY ACCESS PANELS. |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 005 |
(291) |
BATHROOM RECEPTACLE NOT PROPERLY LOCATED (ALL FLOORS)RECEPTACLE NOT PROPERLY LOCATED IN MASTER BATH ROOM T-OUT. |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 006 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS) PANEL LABELS MIX UP T-OUT. |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 007 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS)FLOOR RECEPTACLES WITHIN 6' OF SINK NOT GFCI PROTECTED, IN KITCHENS. |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 008 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS)AFCI NOT PROVIDED FOR SHADES RECEPTACLES, CLOSET RECEPTACLES ANDSMOKE DETECTORS. T-OUT. |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS) TRIMS MISSING IN 1ST FLOOR, 11TH AND 12TH FLOOR. |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 010 |
(999) |
OTHER (ROOF) PANEL MISSING BREAKER TIES. 210.4 |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 011 |
(999) |
OTHER (ROOF) PANEL MISSING ARC FLASH STICKER. 110.16 |
RSLV |
11/27/2017 |
11/27/2017 |
12/28/2017 |
| |
| 012 |
(999) |
OTHER (ALL FLOORS)ALL BATHROOMS GFCI NOT LOCATED WITHIN 36 INCH OF EACH BASIN 210.52 D |
RSLV |
12/28/2017 |
12/28/2017 |
09/13/2018 |
| |
| 013 |
(999) |
OTHER (ALL FLOORS) MC CABLE IN BATH ROOM RECEPTACLES NOT BONDED. 250.118 |
RSLV |
09/13/2018 |
09/13/2018 |
09/18/2018 |