Electrical Application Details for App #: M366085
Premises: 743 BROADWAY MANHATTAN BIN: 1080855     Block: 548   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 60 E 8 ST Census Tract:   57 Health Area:  5700
APT# 18D Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Special Place Name:   APT # 18D
DOB Cross Street(s):   MERCER STREET,    BROADWAY
Status:   C - JOB IS SIGNED OFF 05/26/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/13/2015 4:33 PM
Application Entered:   04/13/2015 Job Start Date:   04/14/2015
Last Change:   05/26/2016 Job End Date:   06/30/2015
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     05/13/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009860 Licensee Name: JOSEPH TODARO
Firm: 002632 Firm Name: TNT ELECTRIC CO., INC.
Firm Phone: 347-763-2342  Firm Address: 41 BOX STREET, STE 301 BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $78.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KATHRYN GROOMS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 CKT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
018  18D  30  25    20  30             
Buildings Total 30  25    20  30                
Total Units : 105 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/04/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  APT # 18D

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M366085
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/27/2015 11/04/2015 CBK A (55) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 03/04/2016 03/04/2016 STP V Y (35) (1)
INSPECTION COMMENTS: CONTRACTOR SHOWED UP LATE SCHEDULING IS WAY OFF
 
(3) 05/13/2016 05/16/2016 TOR C R (15) (0)
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M366085
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (296) PANEL IS LOCATED IN CLOTHES/LINEN CLOSET
(ALL FLOORS) PANEL INSTALL IN CLOTH CLOSET 210.10(D)
RSLV 10/27/2015 10/27/2015 05/13/2016
 
002 (999) OTHER
(ALL FLOORS) PANEL SHARED NOUTRAL NO SIMULTAINOUS TRIO 210.4(B)
RSLV 10/27/2015 10/27/2015 05/13/2016
 
003 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
(ALL FLOORS)BATHROOM SHOWER LIGHT IN BATH ROOM NOT WET LOCATION TYP. 410.10
RSLV 10/27/2015 10/27/2015 05/13/2016
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) PANEL KO SEALS MISSING 110.12(A)
RSLV 10/27/2015 10/27/2015 03/04/2016
 
005 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) CLOSET LED DRIVERS DEFECTIVE WIRING. AMEND 110.2A
RSLV 10/27/2015 10/27/2015 05/13/2016
 
006 (999) OTHER
(FLOOR: 018) NO WORKING SPACE FOR PANEL 110.26
RSLV 03/04/2016 03/04/2016 05/13/2016