BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M365920
Premises: 2 EAST 52 STREET MANHATTAN BIN: 1035479     Block: 1287   Lot: 69
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 653 5 AV Census Tract:   102 Health Area:  4800
N/A Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
DOB Cross Street(s):   EAST 51 STREET,    EAST 52 STREET
Status:   C - JOB IS SIGNED OFF 01/24/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/09/2015 11:54 AM
Application Entered:   04/09/2015 Job Start Date:   06/01/2015
Last Change:   01/24/2018 Job End Date:   07/01/2017
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     01/03/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011239 Licensee Name: DANIEL KIRK
Firm: 003456 Firm Name: TRANSEL ELEV. & ELEC. INC
Firm Phone: 718-609-2600  Firm Address: 30-30 47TH AVENUE, STE 610 L.I.C NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $710.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 511 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GERRY HARBINSON
Owner Business Name: DICKINSON CAMERON
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  5  $750.00
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SUB  1-MACH    90         
EPT                 
ROF  MACHIN    56         
Buildings Total   19     146           
Total Units : 192 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 12/19/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M365920
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/21/2017 11/21/2017 BMP V (125) (2)
INSPECTION COMMENTS: CERTIFIABLE OBJECTION ISSUED. FAIL.
 
(2) 12/19/2017 12/19/2017 PHG H X (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(3) 01/03/2018 01/03/2018 BMP C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M365920
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ROOF) MACHINE ROOMS FOR ELEVATORS 4 & 5. SEC. 250.30(A)(1). XO ONTRANFORMER SECONDARY NOT GROUNDED TO TRANSFORMER CASES.
RSLV 11/21/2017 11/21/2017 01/03/2018
 
002 (999) OTHER
(SUB-CELLAR)CONTROL ROOMS ELEVATORS 1 & 2. SEC. 250.30(A)(1). XO ON TRANSFORMERSECONDARY NOT CONNECTED TO TRANSFORMER CASES.
RSLV 11/21/2017 11/21/2017 01/03/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order