BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M365843
Premises: 166 EAST 87 STREET MANHATTAN BIN: 1047961     Block: 1515   Lot: 7503
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 170 E 87 ST Census Tract:   148.02 Health Area:  3600
19C Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 04/19/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/08/2015 10:19 AM
Application Entered:   04/08/2015 Job Start Date:   04/09/2015
Last Change:   04/19/2016 Job End Date:   10/09/2015
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     04/19/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009791 Licensee Name: JOSEPH B JORDAN
Firm: 004329 Firm Name: GOTHAM WIRING LICENSED
Firm Phone: 718-295-6430  Firm Address: 649A EAST 183RD STREET ELECTRICAL CONTRACTORS IN BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MATTHEW WALKER
Owner Business Name: MYHOME
Authorized Representative:  JOSEPH JORDAN
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
019  19C                 
Buildings Total                   
Total Units : 12 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/21/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING 3 OUTLETS, 6 LIGHTS AND 2 SWITCHES TO EXISTING WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M365843
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/29/2015 11/04/2015 LUF N (45) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW/ CALLED CONTRACTOR NO ANSWER
 
(2) 11/27/2015 12/02/2015 CBK N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SHOW
 
(3) 12/18/2015 12/21/2015 GYM V (50) (3)
INSPECTION COMMENTS: INSPECTED 3 BATH ROOMS ONLY. ( CONTRACTOR NO SHOW)
 
(4) 03/18/2016 03/21/2016 PHG V Y (25) (2)
INSPECTION COMMENTS: BATHROOMS
 
(5) 04/19/2016 04/19/2016 STP C R (45) (0)
INSPECTION COMMENTS: PASS VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: M365843
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 30) OUTLET BOXES ARE NOT SECURED
(FLOOR: 019) BATH ROOMS OUTLET BOXES'
RSLV 12/18/2015 12/18/2015 04/19/2016
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 019) EXISTING PANEL.
RSLV 12/18/2015 12/18/2015 04/19/2016
 
003 (999) OTHER
(FLOOR: 019) BATH ROOMS OUTLET BOXES MISSING EXTENDER ART 314.20
RSLV 12/18/2015 12/18/2015 03/18/2016
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 019) SHEET METAL SCREWS USED IN BATH RM RECEPTACLES 110.3
RSLV 03/18/2016 03/18/2016 04/19/2016
 
005 (999) OTHER
(FLOOR: 019) 2 WIRES UNDER 1 BREAKER FOR BATHROOM FEED 110.3
RSLV 03/18/2016 03/18/2016 04/19/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.