BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M365686
Premises: 4 EAST 53 STREET MANHATTAN BIN: 1035709     Block: 1288   Lot: 7
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 10 E 53 ST Census Tract:   102
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/03/2015 Job Start Date:   03/30/2015
Last Change:   10/17/2025 Job End Date:   03/30/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     03/10/2017      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  Y - PARTLY REMOVED

License #: 013068 Licensee Name: JAVIER VALERA ACERO
Firm: 004377 Firm Name: M.C. ELECTRICAL NY INC
Firm Phone: 929-296-0197  Firm Address: 50-10 49TH STREET, UNIT 1 WOODSIDE NY 11377 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012295 MONAHAN, ADAM 004377 M.C. ELECTRICAL NY INC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $1,165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   OFFICE & COMMERCIAL
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52842     Submittal #: 14A0649  
Owner / Occup:
Owner Business Name: SL GREEN REALTY CORP
Authorized Representative:  ANTHONY MASTROLIA
Relationship To Owner:   VP OF CONSTRUCTION


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  (1) 4000A-10 X (4)#600MCM
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  10  (10) SEST OF (4)#600MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 04/03/2015 Notice: C - CALL TO OFFICE 08/04/2016
Power Issued: 04/03/2015 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M365686
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/11/2015 05/18/2015 TOR A E (90) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 08/02/2016 08/04/2016 TUR V X (30) (2)
INSPECTION COMMENTS: 1200 AMP RETAIL PANEL MOUNTED ON END OF SS-C NOT ON ADVISORY DRAWINGS AND NOT FILED AS SUCH, ALSO IT IS MENTIONED ON M368557 IN COMMENT BOX AND NOT ADVISORY
 
(3) 12/29/2016 12/30/2016 TOR J Y (30) (0)
INSPECTION COMMENTS: NO DRAWING REV 1 SHOWING ACTUAL FOOT PRINT OF THE JOB AND NEW EQUIP. INSTALLED.
 
(4) 03/10/2017 03/13/2017 PHG J Y (45) (0)
INSPECTION COMMENTS: FOR 1200 AMP SW REFER TO APP M368557

OBJECTION FOR APPLICATION #: M365686
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ELECT.RM: NO PANIC DOOR LATCH PROVIDED (BOTH DOORS).. 110.26
OPEN 05/11/2015 05/11/2015
 
002 (999) OTHER
(ALL FLOORS)ELECTR.RM: ARC FLASH WARNING LABELS NOT PROVIDED.. 110.16
RSLV 05/11/2015 05/11/2015 03/10/2017
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) ELECT.RM: KOS SEAL MISSING(4000 AMP SW)
RSLV 05/11/2015 05/11/2015 12/29/2016
 
004 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
(CELLAR)27-3018(B) 1200AMP PANEL NOT FILED AS ADVISORY NOT ON DRAWINGS INONE LINE OR LAYOUT
RSLV 08/02/2016 08/02/2016 03/10/2017
 
005 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(CELLAR) 110.2 1200 AMP PANEL NO T FILED 2ND LEVEL
RSLV 08/02/2016 08/02/2016 03/10/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order