Electrical Application Details for App #: M365619
Premises: 81 10 AVENUE MANHATTAN BIN: 1012277     Block: 687   Lot: 29
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 85 10 AV Census Tract:   99 Health Area:  5500
4TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10011 Community Board:   104
Special Place Name:   GOOGLE
DOB Cross Street(s):   WEST 15 STREET,    WEST 16 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/02/2015 9:50 AM
Application Entered:   04/02/2015 Job Start Date:   04/02/2015
Last Change:   08/22/2025 Job End Date:   09/23/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     11/02/2015      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010777 Licensee Name: GARY DAWES
Firm: 002568 Firm Name: CAMPBELL & DAWES LTD ELEC
Firm Phone: 718-441-6300  Firm Address: 84-48 129TH STREET CONTRACTORS KEW GARDENS NY 11415 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $1,586.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: RELATED MANAGEMENT CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  8  
B. Over #2 to 1/0  6  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  8  
D. 3 Phase Over 225 AMPS  4  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004    165  384    75  660  43  150  180 
Buildings Total 165  384    75  660     43     150     180 
Total Units : 1657 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 11/12/2015
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  C&D JOB # 1215-A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M365619
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/02/2015 11/12/2015 PHG V (200) (13) Y
INSPECTION COMMENTS: DID NOT SEE GRND FOR T-FRMS,OFFICE,MOTORS,HEATERS

OBJECTION FOR APPLICATION #: M365619
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
ELE.RM: #8 ON 60 AMP BREAKER IN MDP.. 240.3
OPEN 11/02/2015 11/02/2015
 
002 (999) OTHER
4FL: IDF-4 SECONDARY CONDUCTOR FROM T-FMR OVER 25' LONG.. 240.21
OPEN 11/02/2015 11/02/2015
 
003 (999) OTHER
4FL: NO FIRE STOP IN ELECTRICAL RM.. 300.21
OPEN 11/02/2015 11/02/2015
 
004 (999) OTHER
4FL: ROMEX FEEDING ELECTRICAL RM LIGHTS.. 590.3
OPEN 11/02/2015 11/02/2015
 
005 (999) OTHER
4FL: SPRINKLER NEXT TO ALL T-FRMS.. 110.26
OPEN 11/02/2015 11/02/2015
 
006 (999) OTHER
4FL: NO WORKING SPACE FOR 75 KVA T-FMR IN HALLWAY.. 110.26
OPEN 11/02/2015 11/02/2015
 
007 (999) OTHER
4FL: ALL 120 GALLON HEATERS NO WORKING SPACE FOR DISCONNECT.. 110.26
OPEN 11/02/2015 11/02/2015
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
4FL: EXIT SIGN BY EXIT HUNG WITH EMT PIPE.. 358.12NO DISCONNECT FOR CONVER MOTOR.. 422.30
OPEN 11/02/2015 11/02/2015
 
009 (999) OTHER
4FL: 2 WIRES UNDER 1 LUG NEUTRAL WIRE IN PANEL RP4KC-2.. 110.3
OPEN 11/02/2015 11/02/2015
 
010 (999) OTHER
4FL: NO G.F.C.I.PROTECTION FOR 120V RECEPTACLES IN WORK STATIONAREAS.. 210.8
OPEN 11/02/2015 11/02/2015
 
011 (999) OTHER
4FL: BROKEN FMC IN IT RM.. 300.10
OPEN 11/02/2015 11/02/2015
 
012 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
4FL: MC CABLE IN 12 X 12 PULL BOX NOT BONDED.. 250.118
OPEN 11/02/2015 11/02/2015
 
013 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
4FL: ALL 277V DISCONNECTS W/CONCENTRIC KO NEEDS BONDED.. 250.97
OPEN 11/02/2015 11/02/2015