BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M365148
Premises: 120 MAC DOUGAL STREET MANHATTAN BIN: 1008696     Block: 540   Lot: 9
   
Application Completed and Certified

Filed: 120 MAC DOUGAL ST Census Tract:   65 Health Area:  5700
1 FL RESTAURANT Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   NEW YORK, NY
DOB Cross Street(s):   BLEECKER STREET,    MINETTA LANE
Status:   C - JOB IS SIGNED OFF 07/27/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/23/2015 7:16 PM
Application Entered:   03/23/2015 Job Start Date:   03/27/2015
Last Change:   07/27/2015 Job End Date:   03/26/2016
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     07/21/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010809 Licensee Name: JOHN L RICKFORD
Firm: 002075 Firm Name: R.J.ELECTRICAL CONTRACTOR
Firm Phone: 718-949-5466  Firm Address: 201-11 LINDEN BLVD ST. ALBANS NY 11412 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $153.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANWER SHAUKAT
Owner Business Name: BEIGMATS BY DELIMARIE,INC
Authorized Representative:  RICKFORD JOHN
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  200A 42CRCT
C. 3 Phase Up to 225 AMPS  1  200A A 42 CRCT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  RES  28  42    28     
Buildings Total 28  42    28            
Total Units : 115 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/18/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING RESTAURANT ON 1 FL FOR RECEPTACLES, FIXTURES, SWITCHES, HOT WATER HEATER AND ONE (1) CENTRAL A/C. NO METER WORK DONE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M365148
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/12/2015 06/18/2015 NRS A (60) (8) Y
INSPECTION COMMENTS: CAFEMARIE EXISTING RISER
 
(2) 06/29/2015 07/07/2015 DNM J Y (40) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 07/21/2015 07/27/2015 WYF C R (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M365148
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
GR: FMC IN PANEL
RSLV 06/12/2015 06/29/2015 07/21/2015
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
GR: 1900 CEILING DRIVER SPLICE BOA NOT BONDED
RSLV 06/12/2015 06/12/2015 06/29/2015
 
003 (252) LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE
GR: 1900 IN CEILING DRIVER SPLICE BOX FOR WOOD PANEL LED-S
RSLV 06/12/2015 06/12/2015 06/29/2015
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
GR: IN CEILING SPLICE BOX ABOVE PANEL
RSLV 06/12/2015 06/12/2015 06/29/2015
 
005 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
GR: 30A RECE. BOXES NOT BONDED AS PER 280.122
RSLV 06/12/2015 06/12/2015 06/29/2015
 
006 (999) OTHER
GR: DOORBELL ON GR. TERMINALOF 30A RECES 110.14
RSLV 06/12/2015 06/12/2015 06/29/2015
 
007 (999) OTHER
OUTS A/C GFCI NOT W/R & NO I USE COVER 406.8
RSLV 06/12/2015 06/29/2015 07/21/2015
 
008 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
OUTS: AC EGC NOT AS PER 250.122
RSLV 06/12/2015 06/12/2015 06/29/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.