BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M365043
Premises: 128 1 AVENUE MANHATTAN BIN: 1005818     Block: 435   Lot: 7
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 128 1 AV Census Tract:   32 Health Area:  6600
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
DOB Cross Street(s):   EAST 7 STREET,    ST MARKS PLACE
Status:   C - JOB IS SIGNED OFF 04/16/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/20/2015 8:41 AM
Application Entered:   03/20/2015 Job Start Date:   03/20/2015
Last Change:   04/16/2016 Job End Date:   03/20/2016
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     12/15/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011990 Licensee Name: DECLAN W DELAHUNTY
Firm: 003662 Firm Name: SHUIR ELEC'L CONTR'S CORP
Firm Phone: 718-414-4840  Firm Address: 4360 BULLARD AVENUE BRONX NY 10466 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $361.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESTRAUNT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GERALD SAN JOSE
Owner Business Name: NOREETUH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  ONE 300AMP MAIN BREAKER
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  ONE SET OF 350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  ONE 100AMP PANEL
D. 3 Phase Over 225 AMPS  1  ONE 300AMP PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10             
GND    15  25             
Buildings Total 25  33    11                
Total Units : 75 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/20/2015 Notice: 1 - FIRST NOTICE 11/12/2015
Power Issued: 03/20/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL 300AMP PANEL & METER & REWIRE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M365043
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/01/2015 10/06/2015 ECH A E (45) (9) Y
INSPECTION COMMENTS: NONE
 
(2) 11/02/2015 11/12/2015 BUR A Y E (40) (2) Y
INSPECTION COMMENTS: NONE
 
(3) 12/15/2015 12/16/2015 NRS C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M365043
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: WIRES DOUBLED UP ON BREAKER IN SUB-PANEL.. 110.14
RSLV 10/01/2015 10/01/2015 11/02/2015
 
002 (999) OTHER
BSMT: EQUIPMENT NOT BONDED ON LINE SIDE OF SERVICE.. 250.4
RSLV 10/01/2015 10/01/2015 11/02/2015
 
003 (999) OTHER
(ALL FLOORS) BSMT: DERATING NEEDED IN SUB-PANEL.. 310.15
RSLV 10/01/2015 11/02/2015 12/15/2015
 
004 (999) OTHER
OUTSIDE: WR RECEPTACLES NEEDED OUTSIDE NEAR COMPRESSORS
RSLV 10/01/2015 10/01/2015 11/02/2015
 
005 (999) OTHER
KITCHEN: G.F.C.I.RECEPTACLES NEEDED IN KITCHEN CEILING/THROUGH-OUT210.8B
RSLV 10/01/2015 10/01/2015 11/02/2015
 
006 (999) OTHER
BAR: RECEPTACLE LESS THAN 6' FROM SINK NEEDS G.F.C.I.. 210.8A
RSLV 10/01/2015 10/01/2015 11/02/2015
 
007 (999) OTHER
THROUGH-OUT: RECEPTACLE SET BACK ON WOOD THROUGH-OUT MORE THAN A1/4" WITHOUT PROTECTION THROUGH-OUT.. 314.20
RSLV 10/01/2015 10/01/2015 11/02/2015
 
008 (999) OTHER
T-OUT: RECEPTACLES NOT GROUNDED PROPERLY.. 350.146
RSLV 10/01/2015 10/01/2015 11/02/2015
 
009 (999) OTHER
BSMT: WIRES DOUBLED UP ON TERMINAL IN DRIVER ENCLOSURE.. 110.14
RSLV 10/01/2015 10/01/2015 11/02/2015
 
010 (999) OTHER
(ALL FLOORS)CELLAR: MC GREEN CONDUCTOR USED AS UNGROUNDED CONDUCTOR NOT PERMITT-ED.. 250.119
RSLV 11/02/2015 11/02/2015 12/15/2015
 
011 (999) OTHER
(ALL FLOORS) CELLAR: MULTIWIRE CKTS NOT TERMINATED PROPERLY.. 210.4
RSLV 11/02/2015 11/02/2015 12/15/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back