| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
ONE 300AMP MAIN BREAKER |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
ONE SET OF 350MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
ONE 100AMP PANEL |
| D. 3 Phase Over 225 AMPS |
1 |
ONE 300AMP PANEL |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: WIRES DOUBLED UP ON BREAKER IN SUB-PANEL.. 110.14 |
RSLV |
10/01/2015 |
10/01/2015 |
11/02/2015 |
| |
| 002 |
(999) |
OTHER BSMT: EQUIPMENT NOT BONDED ON LINE SIDE OF SERVICE.. 250.4 |
RSLV |
10/01/2015 |
10/01/2015 |
11/02/2015 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS) BSMT: DERATING NEEDED IN SUB-PANEL.. 310.15 |
RSLV |
10/01/2015 |
11/02/2015 |
12/15/2015 |
| |
| 004 |
(999) |
OTHER OUTSIDE: WR RECEPTACLES NEEDED OUTSIDE NEAR COMPRESSORS |
RSLV |
10/01/2015 |
10/01/2015 |
11/02/2015 |
| |
| 005 |
(999) |
OTHER KITCHEN: G.F.C.I.RECEPTACLES NEEDED IN KITCHEN CEILING/THROUGH-OUT210.8B |
RSLV |
10/01/2015 |
10/01/2015 |
11/02/2015 |
| |
| 006 |
(999) |
OTHER BAR: RECEPTACLE LESS THAN 6' FROM SINK NEEDS G.F.C.I.. 210.8A |
RSLV |
10/01/2015 |
10/01/2015 |
11/02/2015 |
| |
| 007 |
(999) |
OTHER THROUGH-OUT: RECEPTACLE SET BACK ON WOOD THROUGH-OUT MORE THAN A1/4" WITHOUT PROTECTION THROUGH-OUT.. 314.20 |
RSLV |
10/01/2015 |
10/01/2015 |
11/02/2015 |
| |
| 008 |
(999) |
OTHER T-OUT: RECEPTACLES NOT GROUNDED PROPERLY.. 350.146 |
RSLV |
10/01/2015 |
10/01/2015 |
11/02/2015 |
| |
| 009 |
(999) |
OTHER BSMT: WIRES DOUBLED UP ON TERMINAL IN DRIVER ENCLOSURE.. 110.14 |
RSLV |
10/01/2015 |
10/01/2015 |
11/02/2015 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS)CELLAR: MC GREEN CONDUCTOR USED AS UNGROUNDED CONDUCTOR NOT PERMITT-ED.. 250.119 |
RSLV |
11/02/2015 |
11/02/2015 |
12/15/2015 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS) CELLAR: MULTIWIRE CKTS NOT TERMINATED PROPERLY.. 210.4 |
RSLV |
11/02/2015 |
11/02/2015 |
12/15/2015 |