BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M364823
Premises: 347 BOWERY MANHATTAN BIN: 1090232     Block: 459   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 347 BOWERY Census Tract:   38 Health Area:  6500
GROUND Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
Related Job Number:    121185289
DOB Cross Street(s):   EAST 3 STREET,    COOPER SQUARE
Status:   C - JOB IS SIGNED OFF 08/16/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/16/2015 11:09 AM
Application Entered:   03/16/2015 Job Start Date:   03/16/2015
Last Change:   08/16/2018 Job End Date:   09/30/2016
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     06/26/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011685 Licensee Name: VALENTIN S BOROVINOV
Firm: 003335 Firm Name: VALMAR ELECTRIC CORP.
Firm Phone: 718-707-0091  Firm Address: 5-44 47TH AVE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $2,092.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 6 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LOLI-GHETTI GLAUCO
Owner Business Name: 347 BOWERY OWNER LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  1  4#600
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  4   2-#3, 3-PHASE, 4-WIRE, 2
B. Over #2 to 1/0  5  4-#1, 3-PHASE, 4-WIRE, 1-
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  7  1-3SETS 600KCMIL CU, 3-PH
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  8  4#2
D. 3 Phase Over 225 AMPS  2  4/0
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    62  28    40    173         
001    51    17           
002    35  54    13           
003  49  38             
004  49  38             
005  49  38             
006  49  38             
007  49  38             
008  49  38             
009  49  38             
010  49  38             
011  27  35             
012  27  41             
013  25  27             
ROF    16  10        40         
Buildings Total 635  506    132       230           
Total Units : 1503 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 5 #10-Wire 3
Existing Meters 0 + New Meters 8 - Removed Meters 0 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/16/2015 Notice:  
Power Issued: 03/16/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M364823
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/18/2018 05/21/2018 BMP J (260) (5)
INSPECTION COMMENTS: SERVICE, BASEMENT, ROOF, A/CS, AND GENERATOR COMPLETED WITH OBJECTIONS NOTED. APTS. 3R AND 5R COMPLETED. JOB IN PROGRESS.
 
(2) 06/26/2018 06/27/2018 BMP C R (140) (0)
INSPECTION COMMENTS: CERTIFIED.

OBJECTION FOR APPLICATION #: M364823
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)SEC. 695.4(B)(1)(1). AMENDMENT. GROUND-FAULT AND SHORT-CIRCUITPROTECTION FOR FIRE PUMP RATED IN EXCESS OF 6 TIMES MOTOR FLC.
RSLV 05/18/2018 05/18/2018 06/26/2018
 
002 (999) OTHER
(BASEMENT)SEC. 230.7. FIRE PUMP SERVICE CONDUCTORS IN SAME TROUGH ABOVESERVICE ENCLOSURE WITH "OTHER" CONDUCTORS.
RSLV 05/18/2018 05/18/2018 06/26/2018
 
003 (999) OTHER
(BASEMENT)SEC. 250.122.(D)(1). EQUIPMENT GROUNDING CONDUCTOR FOR FIRE PUMP ISTOO SMALL.
RSLV 05/18/2018 05/18/2018 06/26/2018
 
004 (999) OTHER
(BASEMENT)250.24.(C). NEUTRAL CONDUCTOR MUST BE RUN TO FIRE PUMP SERVICEDISCONNECT.
RSLV 05/18/2018 05/18/2018 06/26/2018
 
005 (999) OTHER
(BASEMENT) 250.10. GROUND ROD CONNECTION EXPOSED TO PHYSICAL DAMAGE.
RSLV 05/18/2018 05/18/2018 06/26/2018