BIS Menu  |  Applications  |  Inspection Request - Work Order Overview  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M364795
Premises: 1200 FDR DRIVE MANHATTAN BIN: 1088433     Block: 962   Lot: 80
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1200 FDR DR Census Tract:   62 Health Area:  6000
NEW BUILDING JOB@9430 Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10016 Community Board:   106
Special Place Name:   NYU ENERGY BUILDING
Related Job Number:    120448293
DOB Cross Street(s):   EAST 30 STREET,    EAST 34 STREET
Status:   C - JOB IS SIGNED OFF 03/03/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/15/2015 7:38 PM
Application Entered:   03/15/2015 Job Start Date:   03/16/2015
Last Change:   03/03/2017 Job End Date:   05/31/2015
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     02/22/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010613 Licensee Name: ROBERT LIPIRO
Firm: 000553 Firm Name: FRED GELLER ELEC'L INC.
Firm Phone: 718-350-3900  Firm Address: 54-15 38TH AVENUE WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RICHARD COHEN
Owner Business Name: NYU HOSPITAL CENTER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  46  SETS 8@#2,27@#3,6@#6,5@#8
B. Over #2 to 1/0  1  SET 1/0
C. Over 1/0 to 250 MCM  1  SET 3/0
D. Over 250 MCM  32  SETS 25@600, 7@750
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  40  1@200,31@100,8@60AMP
D. 3 Phase Over 225 AMPS  15  1@800,1@600,11@400,2@300A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    85  29    16  110  10  45 
001    10    21  16  16  150 
002    20    31             
003    85  20    25  131  12  45  60  45 
005    37  13    37  13  14  15     
006    30    109          15 
Buildings Total 267  73    58  439     76     101     255 
Total Units : 1269 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/24/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACING APPLICATION #M332965. BREAKING OUT 4TH, 4MEZZ WHICH HAS NOW BEEN TAKEN OUT AS APPLICATION #M364794

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M364795
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/15/2015 06/24/2015 GYM A (130) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 02/22/2017 02/22/2017 MQY C R (120) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED...RE:M364794 FOR 4TH FLOOR AND MEZ. RE:M362092 FOR ADVISORY BOARD

OBJECTION FOR APPLICATION #: M364795
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)2 FLOOR T6 112.5 KVA 13 GROUNDING ELECTRICAL CONDUCTOR NOT AS PERTAB 250.66
RSLV 06/15/2015 06/15/2015 02/22/2017
 
002 (999) OTHER
(ALL FLOORS)2 FLOOR T6 112.5 KVA K 13 GROUNDING RACEWAY NOT CONTINUOUS ART250.6
RSLV 06/15/2015 06/15/2015 02/22/2017
 
003 (999) OTHER
(ALL FLOORS) ALL FLOOR OUTLET BOXES NOT BONDED AS PER ART. 250.8
RSLV 06/15/2015 06/15/2015 02/22/2017
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) 4 FLOOR PPH EB 4AL PANEL TRIM MISSING
RSLV 06/15/2015 06/15/2015 02/22/2017
 
005 (999) OTHER
(ALL FLOORS)TS-30 KVA K13 TRANSFORMER GROUNDING RACEWAY NOT CONTINUOUS ART250.64
RSLV 06/15/2015 06/15/2015 02/22/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Inspection Request - Work Order Overview  |  Electrical Inspection Work Order  |  Back