BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M364661
Premises: 281 BROADWAY MANHATTAN BIN: 1087951     Block: 149   Lot: 7502
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 285 BROADWAY Census Tract:   21 Health Area:  7700
BROADWAY Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
Related Job Number:    122121042
DOB Cross Street(s):   CHAMBERS STREET,    READE STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/12/2015 6:52 AM
Application Entered:   03/12/2015 Job Start Date:   03/12/2015
Last Change:   08/22/2025 Job End Date:   05/29/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     08/02/2019      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 011363 Licensee Name: JACOB NAFTALY
Firm: 002781 Firm Name: JACOBS ELECTRIC CORP.
Firm Phone: 718-533-9355  Firm Address: 37-31 58TH STREET, STE A-11 WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $280.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122121042
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DR KUO
Owner Business Name: PHYSICAL THERAPY
Authorized Representative:  GERARD COFFEY
Relationship To Owner:   PROJECT SUPER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  347  118  29  69             
Buildings Total 347  118  29  69                
Total Units : 572 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 03/12/2015 Notice: C - CALL TO OFFICE 12/11/2017
Power Issued: 03/12/2015 Response:  

Follow-Up:
Contractor's Comments:  FURNISH AND INSTALL 2 NEW ELECTRICAL PANELS USING EXISTING SERVICE. FURNISH AND INSTALL GENERAL POWER AND LIGHTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M364661
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/07/2016 06/07/2016 STP V (55) (8)
INSPECTION COMMENTS: FAIL. DID NOT SEE HEATERS OR AC EQUIPMENT. CONTRACTOR DID NOT FOR HEATERS MOTORS OR FEEDERS .
 
(2) 08/03/2016 08/04/2016 EDB V R (51) (1)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(3) 12/11/2017 12/11/2017 STP J X (30) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS
 
(4) 08/02/2019 08/02/2019 ASK N (10) (0) Y
INSPECTION COMMENTS: FAIL. CALL CONTRACTOR. NO SHOW.

OBJECTION FOR APPLICATION #: M364661
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) DS OVERFUSED AT 250 AMPS 250.4
RSLV 06/07/2016 06/07/2016 08/03/2016
 
002 (999) OTHER
(BASEMENT) DS NEUTRAL BONDED TO ENCLOSURE 250.24
RSLV 06/07/2016 06/07/2016 08/03/2016
 
003 (999) OTHER
(BASEMENT) NO FIRE STOPPING FOR PIPE ELECTRIC RM 300.21
RSLV 06/07/2016 06/07/2016 08/03/2016
 
004 (999) OTHER
(GROUND FLOOR) NO 90 DEGREE SWING OF PANEL COVER 110.26
RSLV 06/07/2016 06/07/2016 08/03/2016
 
005 (999) OTHER
(GROUND FLOOR) NO ARC FLASH STICKERS ON PANELS 110.16
RSLV 06/07/2016 06/07/2016 08/03/2016
 
006 (999) OTHER
(GROUND FLOOR) NO GFI 6 FT OF SINK EXAM RM AND SLOP SINK 210.8
RSLV 06/07/2016 06/07/2016 08/03/2016
 
007 (999) OTHER
(GROUND FLOOR) TEMP NOT REMOVED FROM RECEPTION AREA 590.3
RSLV 06/07/2016 06/07/2016 08/03/2016
 
008 (999) OTHER
(GROUND FLOOR) NO BARRIER FOR CLASS 2 LED AND 120VOLT CKTS 725.136
RSLV 06/07/2016 06/07/2016 08/03/2016
 
009 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(CELLAR)CONTRACTOR INSTALLED 2ND FUSE 250 A AND CHANGE TO 200 A IN 400 ATRAS-S
OPEN 08/03/2016 08/03/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order