BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M364614
Premises: 38 EAST 85 STREET MANHATTAN BIN: 1046824     Block: 1496   Lot: 54
   
Application Completed and Certified

Filed: 1133 MADISON AV Census Tract:   150.01 Health Area:  3600
GROUND FLOOR/BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
Related Job Number:    122193027
DOB Cross Street(s):   EAST 84 STREET,    EAST 85 STREET
Status:   C - JOB IS SIGNED OFF 09/15/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/10/2015 9:39 PM
Application Entered:   03/10/2015 Job Start Date:   03/11/2015
Last Change:   09/15/2015 Job End Date:   03/10/2016
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     09/03/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 011621 Licensee Name: JAMES P RYAN
Firm: 003160 Firm Name: J.P. RYAN ELECTRIC, INC.
Firm Phone: 718-393-7516  Firm Address: 38-32 29TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $591.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122193027
Building Used As:   Z - Other
Store / Other:   BANK
Special Cert Approval:   E - EMERGENCY LIGHTING LOCAL LAW 16/84
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT WALSH
Owner Business Name: TD BANK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  3/0
D. 3 Phase Over 225 AMPS  1  500MCM
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
GND    37  42    26     
Buildings Total 37  42    26            
Total Units : 114 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/10/2015 Notice: 1 - FIRST NOTICE 08/31/2015
Power Issued: 03/10/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M364614
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/24/2015 08/31/2015 TOR A E (90) (7) Y
INSPECTION COMMENTS: NONE
 
(2) 09/03/2015 09/09/2015 PHG C R G (50) (0) Y
INSPECTION COMMENTS: REMOVED ALL OBJECTIONS

OBJECTION FOR APPLICATION #: M364614
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
OUTSIDE A.C. OVERFUSED AT 60A 440.22 (C)
RSLV 08/24/2015 08/24/2015 09/03/2015
 
002 (999) OTHER
OUTSIDE A.C. OVERFUSED AT 40A 440.22
RSLV 08/24/2015 08/24/2015 09/03/2015
 
003 (999) OTHER
OUTSIDE A.C. OVERFUSED AT 30A 440.22 (C)
RSLV 08/24/2015 08/24/2015 09/03/2015
 
004 (999) OTHER
OUTSIDE RECEPTACLE NOT W.R. 406.8
RSLV 08/24/2015 08/24/2015 09/03/2015
 
005 (999) OTHER
GROUND SEALTIGHT MORE THAN 18" FIR IFFUCE FYRBUTURE 605 AMEND MENTS
RSLV 08/24/2015 08/24/2015 09/03/2015
 
006 (999) OTHER
GROUND CONDUCTORS NOT PROPERLY COLOR CODED. 210.5
RSLV 08/24/2015 08/24/2015 09/03/2015
 
007 (999) OTHER
GROUND ELECTRIC HEATER OVERFUSED AT 70A 240.4
RSLV 08/24/2015 08/24/2015 09/03/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order