BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M364410
Premises: 206 AVENUE OF THE AMERICAS MANHATTAN BIN: 1008101     Block: 519   Lot: 44
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 210 6 AV Census Tract:   37 Health Area:  6800
APT 5 Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   CHARLTON STREET,    KING STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/04/2015 2:07 PM
Application Entered:   03/04/2015 Job Start Date:   03/04/2015
Last Change:   08/22/2025 Job End Date:   03/20/2015
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     03/01/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DANIELLE RUBIN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      10                   
Buildings Total   10                      
Total Units : 10 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/01/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M364410
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/12/2015 06/23/2015 WYF N (30) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR SAID THEY DID NOT KNOW ABOUT APPOINTMENT
 
(2) 06/29/2015 07/07/2015 DNM N (20) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW
 
(3) 03/01/2017 03/01/2017 PHG V (20) (6)
INSPECTION COMMENTS: CONTRACTOR TO FILE FOR PANEL LIGHTS ECT

OBJECTION FOR APPLICATION #: M364410
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(FLOOR: 005) BONDING JUMPER FOR PANEL NOT REMOVED 250.24
OPEN 03/01/2017 03/01/2017
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 005) ZIP CORD USED FOR UCL 400.8
OPEN 03/01/2017 03/01/2017
 
003 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 005) KITCHEN OUTLETS SHARED WITH OTHER 210.52
OPEN 03/01/2017 03/01/2017
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 005) MC CABLE IN PANEL NOT BONDED 250.148
OPEN 03/01/2017 03/01/2017
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 005) NO DIRECTORY
OPEN 03/01/2017 03/01/2017
 
006 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(FLOOR: 005) IMPROPER PLACEMENT KITCHEN COUNTER RECEPTACLES 210.52
OPEN 03/01/2017 03/01/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order