Electrical Application Details for App #: M364291
Premises: 244 7 AVENUE MANHATTAN BIN: 1014176     Block: 774   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 252 7 AV Census Tract:   91 Health Area:  5200
APT 11Q Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):   WEST 24 STREET,    WEST 25 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/02/2015 12:10 PM
Application Entered:   03/02/2015 Job Start Date:   03/02/2015
Last Change:   10/07/2025 Job End Date:   03/29/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DHANESHWAR BISSOON       On     07/29/2025      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $45.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PETER HIRSCH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011    20                 
Buildings Total 20                    
Total Units : 33 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 07/30/2025
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M364291
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/08/2025 07/09/2025 KVF N (20) (0) Y
INSPECTION COMMENTS: NO ACCESS. ATOI CALLED CONTRACTOR BUT SPOKE WITH CONTRACTOR'S REPRESENTATIVE. REPRESENTATIVE STATED THEY WOULD HAVE TO RESCHEDULE INSPECTION DUE TO NOT HAVING ELECTRICIAN MAKE IT FOR INSPECTION. UNABLE TO CONDUCT VISUAL INSPECTION DUE TO NO ACCESS TO APARTMENT WHERE SCOPE OF WORK WAS DONE. PROCEEDING AS DIRECTED BY OFFICE.
 
(2) 07/29/2025 07/30/2025 DWB V (20) (5)
INSPECTION COMMENTS: ATOI BENARD-INSPECTION COMPLETE, AS PER CONTRACTOR ON JOB SITE, ELECTRICAL WORK WAS PERFORM AT KITCHEN ONLY, TO REPLACING DEVICES WITH CIRCUIT. OBJECTION ISSUED.
 
(3) ? (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application

OBJECTION FOR APPLICATION #: M364291
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(FLOOR: 011)EQUIPMENT GROUNDING AND EQUIPMENT GROUNDING CONDUCTOR FIXED IN PLACE250.110/ #4 EGC NOT TERMINATE AT PANELS.
RSLV 07/29/2025 07/29/2025
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 011)APT 11Q-JUNCTION BOXES SET BACK (COMB FLUSH, NON-COMB ) (406.4REC) 314.20/WITH WOOD AT KITCHEN COUNTER TOP.
RSLV 07/29/2025 07/29/2025
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 011)314.20 JUNCTION RECESSED MORE THAN 1/4"/ AT KITCHEN COUNTER TOP.
RSLV 07/29/2025 07/29/2025
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 011)314.20,404.10(B), SNAP SWITCHES NOT BONDED/ SET BACK AT KITCHENCOUNTER
RSLV 07/29/2025 07/29/2025
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 011)210.8, KITCHEN COUNTER TOP RECEPTACLE INSTALLED NOT GFCI PROTECTED.
RSLV 07/29/2025 07/29/2025