BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M363934
Premises: 40 PECK SLIP MANHATTAN BIN: 1001338     Block: 97   Lot: 31
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 40 PECK SLIP Census Tract:   15.01 Health Area:  7700
GROUND,2ND,3RD&4TH FLOORS Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Special Place Name:   SUPERIOR OFFICERS ASSOCIATION
DOB Cross Street(s):   FRONT STREET,    SOUTH STREET
Status:   C - JOB IS SIGNED OFF 04/27/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/20/2015 2:58 PM
Application Entered:   02/20/2015 Job Start Date:   02/20/2015
Last Change:   04/27/2018 Job End Date:   11/30/2015
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     03/01/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011850 Licensee Name: JAMES P ST. JOHN
Firm: 003455 Firm Name: PATRIOT ELECTRIC CORP
Firm Phone: 718-736-8733  Firm Address: 15-17 126TH STREET 3RD FLOOR COLLEGE POINT NY 11356 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $295.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TED O'ROURKE
Owner Business Name: ICS BUILDERS
Authorized Representative:  TED O'ROURKE
Relationship To Owner:   OWNER'S REP.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/20/2015 Notice: C - CALL TO OFFICE 03/28/2017
Power Issued: 02/20/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M363934
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/28/2016 09/29/2016 MQY V (34) (5)
INSPECTION COMMENTS: NO ACCESS TO GEC OR SUPPLEMENTAL. CHECK GROUND AND BONDING
 
(2) 12/01/2016 12/05/2016 PHG H X (44) (0) Y
INSPECTION COMMENTS: ROOF ONLY DID NOT INSPECT BRANCH WIRING
 
(3) 03/28/2017 03/28/2017 CBK J X (50) (0) Y
INSPECTION COMMENTS: OBJECTIONS NOT REMOVED.
 
(4) 03/01/2018 03/02/2018 TOR C R (40) (0)
INSPECTION COMMENTS: PASS.

OBJECTION FOR APPLICATION #: M363934
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR)UTILITY MANHOLE COVER IS NOT ACCESSIBLE, STAIRS BUILT DIRECTLY ONMANHOLE COVER (110.73)
RSLV 09/28/2016 09/28/2016 03/01/2018
 
002 (999) OTHER
(ROOF) NEUTRAL BONDED AFTER SS IN PANEL (250.24)
RSLV 09/28/2016 09/28/2016 03/01/2018
 
003 (999) OTHER
(ROOF) MAIN BONDING JUMPER MISSING FROM SS (250.92)(250.24)
RSLV 09/28/2016 09/28/2016 03/01/2018
 
004 (999) OTHER
(ROOF) UTILITY VAULT NOT ACCESSIBLE (BOTTOM STAIR BUILT ON VAULT
RSLV 09/28/2016 09/28/2016 03/01/2018
 
005 (999) OTHER
(ROOF) NEUTRAL BONDING MISSING FROM SS (250.92)
RSLV 09/28/2016 09/28/2016 03/01/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order