| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
3 |
|
| B. Each Additional 10 Floors Or Less |
3 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(181) |
DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED (ALL FLOORS) NO DISCONNECT NEXT TO MOTORS IN SHAFT WAY 620.51 |
RSLV |
08/17/2018 |
08/17/2018 |
10/10/2019 |
| |
| 002 |
(127) |
NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM (ROOF) TWO XFRMS NO GROUND PROVIDED 450.5 |
RSLV |
08/17/2018 |
08/17/2018 |
10/10/2019 |
| |
| 003 |
(281) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (ROOF) ROOF ELEVATOR MECHANICAL ROOM. 250.64(C) EGC NOT CONTINUOUS.ELEVATOR XFMR 1P48512 AND 1P48513 |
RSLV |
03/04/2019 |
03/04/2019 |
07/19/2019 |
| |
| 004 |
(999) |
OTHER (ROOF) ROOF . ELEVATOR MECHANICAL ROOM . 250.30 (A)(5) ELEVATOR XFMR1P48512 AND 1P48513 ( SEPARATELY DERIVED SYSTEM NOT GROUNDING) |
RSLV |
03/04/2019 |
03/04/2019 |
10/10/2019 |
| |
| 005 |
(999) |
OTHER (ROOF)RE BAR ON ROOF NOT LISTED FOR USE AS GROUNDING ELECTRODE 250.52 |
RSLV |
07/19/2019 |
07/19/2019 |
10/10/2019 |
| |
| 006 |
(999) |
OTHER (ROOF)PROVIDE SPEC FOR MOTOR NAMEPLATE AMPS LISTING VOLTS ETC. 110.3 |
RSLV |
07/19/2019 |
07/19/2019 |
10/10/2019 |
| |
| 007 |
(999) |
OTHER (ROOF)RE BAR ON ROOF NOT LISTED FOR USE AS GROUNDING ELECTRODE 250.52 |
RSLV |
07/19/2019 |
07/19/2019 |
10/10/2019 |
| |
| 008 |
(999) |
OTHER (ROOF)PROVIDE SPEC FOR MOTOR NAMEPLATE AMPS LISTING VOLTS ETC. 110.3 |
RSLV |
07/19/2019 |
07/19/2019 |
10/10/2019 |
| |
| 009 |
(999) |
OTHER (ROOF) SELF-CERTIFIED RE-BAR AS APPROVED ELECTRODE. 250. 52 |
RSLV |
10/10/2019 |
10/10/2019 |
11/04/2019 |