Electrical Application Details for App #: M363516
Premises: 1162 2 AVENUE MANHATTAN BIN: 1090528     Block: 1436   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 301 E 61 ST Census Tract:   110 Health Area:  4900
301 EAST 61 ST CCB924,925,926 Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
Related Job Number:    121163436
DOB Cross Street(s):    2 AVENUE,    PEDESTRIAN AND BIKE PATH LINK
Status:   C - JOB IS SIGNED OFF 12/04/2019 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/09/2015 10:31 AM
Application Entered:   02/09/2015 Job Start Date:   03/01/2015
Last Change:   12/04/2019 Job End Date:   09/30/2016
Appointment Status:   
Last Inspection By:   RIVERA, F       On     11/04/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010552 Licensee Name: JOSEPH H BRAMAN
Firm: 004092 Firm Name: TK ELEVATOR CORPORATION
Firm Phone: 212-947-8800  Firm Address: 519 8TH AVENUE, 6TH FL NEW YORK NY 10018 

Work Started or Filed by Others: YES
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $664.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   V1-VACANT LAND
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TERANCE W CARROLL
Owner Business Name: ONEKEY LLC
Authorized Representative:  TERRANCE W CARROLL
Relationship To Owner:   VICE PRESIDENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  3  
B. Each Additional 10 Floors Or Less  3  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/10/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M363516
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/26/2018 06/26/2018 TUR N (90) (0) Y
INSPECTION COMMENTS: NO ELECTRICIAN ON SITE TO OPEN EQUIPMENT, CALLED ELECTRICIAN NO PROGRESS
 
(2) 08/17/2018 08/21/2018 PHG V (90) (2)
INSPECTION COMMENTS: 2 XFRMS ON ROOF NO GROUND
 
(3) 03/04/2019 03/04/2019 CDX V X (55) (2)
INSPECTION COMMENTS: FAIL
 
(4) 07/19/2019 07/20/2019 STP V Y (40) (4)
INSPECTION COMMENTS: FAIL. CONTRACTOR TO PROVIDE PROPER SCHEMATIC TO COMPLY WITH OBJECTION WRITTEN FOR DISCONNECT IN SHAFT WITHIN THE CONTROL CIRCUIT. 620.51. EFFECTIVE GROUND FAULT CURRENT PATH 250.4
 
(5) 08/30/2019 08/30/2019 DNM N (36) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW.
 
(6) 10/10/2019 10/10/2019 CBK V R (45) (1)
INSPECTION COMMENTS: CONTRACTOR NEED TO SELF-CERTIFIED RE-BAR AS AS RELIABLE ELECTRODE.
 
(7) 11/04/2019 11/04/2019 FRI C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000025593

OBJECTION FOR APPLICATION #: M363516
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (181) DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED
(ALL FLOORS) NO DISCONNECT NEXT TO MOTORS IN SHAFT WAY 620.51
RSLV 08/17/2018 08/17/2018 10/10/2019
 
002 (127) NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM
(ROOF) TWO XFRMS NO GROUND PROVIDED 450.5
RSLV 08/17/2018 08/17/2018 10/10/2019
 
003 (281) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(ROOF) ROOF ELEVATOR MECHANICAL ROOM. 250.64(C) EGC NOT CONTINUOUS.ELEVATOR XFMR 1P48512 AND 1P48513
RSLV 03/04/2019 03/04/2019 07/19/2019
 
004 (999) OTHER
(ROOF) ROOF . ELEVATOR MECHANICAL ROOM . 250.30 (A)(5) ELEVATOR XFMR1P48512 AND 1P48513 ( SEPARATELY DERIVED SYSTEM NOT GROUNDING)
RSLV 03/04/2019 03/04/2019 10/10/2019
 
005 (999) OTHER
(ROOF)RE BAR ON ROOF NOT LISTED FOR USE AS GROUNDING ELECTRODE 250.52
RSLV 07/19/2019 07/19/2019 10/10/2019
 
006 (999) OTHER
(ROOF)PROVIDE SPEC FOR MOTOR NAMEPLATE AMPS LISTING VOLTS ETC. 110.3
RSLV 07/19/2019 07/19/2019 10/10/2019
 
007 (999) OTHER
(ROOF)RE BAR ON ROOF NOT LISTED FOR USE AS GROUNDING ELECTRODE 250.52
RSLV 07/19/2019 07/19/2019 10/10/2019
 
008 (999) OTHER
(ROOF)PROVIDE SPEC FOR MOTOR NAMEPLATE AMPS LISTING VOLTS ETC. 110.3
RSLV 07/19/2019 07/19/2019 10/10/2019
 
009 (999) OTHER
(ROOF) SELF-CERTIFIED RE-BAR AS APPROVED ELECTRODE. 250. 52
RSLV 10/10/2019 10/10/2019 11/04/2019