Electrical Application Details for App #: M362878
Premises: 501 MADISON AVENUE MANHATTAN BIN: 1035711     Block: 1288   Lot: 21
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 501 MADISON AV Census Tract:   102 Health Area:  4800
20TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
DOB Cross Street(s):   EAST 52 STREET,    EAST 53 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/20/2015 1:14 PM
Application Entered:   01/20/2015 Job Start Date:   01/21/2015
Last Change:   08/22/2025 Job End Date:   02/20/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DHANESHWAR BISSOON       On     07/25/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 012309 Licensee Name: DOMENICO UNGARO
Firm: 004083 Firm Name: RELIABLE ELEC OF NYC, INC
Firm Phone: 718-227-2008  Firm Address: 133 STORER AVENUE STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $73.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RICHARD BROWNE
Owner Business Name: COLLIERS INTERNATIONAL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
020    20  98    20             
Buildings Total 20  98    20                
Total Units : 143 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 07/25/2019
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M362878
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/23/2015 04/28/2015 PHG A (60) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 07/27/2015 08/03/2015 TOR A Y (30) (1) Y
INSPECTION COMMENTS: NONE
 
(3) 07/10/2019 07/10/2019 PHG H X (30) (0) Y
INSPECTION COMMENTS: FAIL
 
(4) 07/25/2019 07/25/2019 DWB V X (50) (5)
INSPECTION COMMENTS: OBJECTION ISSUED.

OBJECTION FOR APPLICATION #: M362878
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
20FL: NO HANDLE TIES PROVIDED FOR MULTIWIRE CKT.. 210.4
OPEN 04/23/2015 07/27/2015
 
002 (999) OTHER
20FL: 2 NEUTRAL WIRES UNDER 1 LUG.. 110.2
RSLV 04/23/2015 04/23/2015 07/27/2015
 
003 (999) OTHER
20FL: TROUGH NOT AS 376.22
RSLV 04/23/2015 04/23/2015 07/27/2015
 
004 (999) OTHER
ELECTRIC CLOSET: WIRES NOT GROUPED 210.4
OPEN 07/27/2015 07/27/2015
 
005 (229) SPLICE BOXES NOT ACCESSIBLE
(FLOOR: 020)314.29, NYC JUNCTION BOXES ARE NOT ACCESSIBLE, THRU-OUT.
OPEN 07/25/2019 07/25/2019
 
006 ( 31) MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN OUTLET BOX
(FLOOR: 020)314.16, LIGHT FIXTURE JUNCTION ARE OVER CROWDED. BOX FILL
OPEN 07/25/2019 07/25/2019
 
007 (999) OTHER
(FLOOR: 020)AM 605.6, SEAL TIGHT INSTALLED AT FURNITURE, ARE IN EXCESSIVELENGTH, THRU-OUT.
OPEN 07/25/2019 07/25/2019
 
008 (999) OTHER
(FLOOR: 020)410.40, LIGHT FIXTURE INSTALLED AT OPEN SPACE ARE NOT GROUNDED.
OPEN 07/25/2019 07/25/2019
 
009 (999) OTHER
(FLOOR: 020)CONTRACTOR TO MAKE PROPER ARRANGEMENT TO ACCESS SPACE. FURTHERINSPECTION NEEDED
OPEN 07/25/2019 07/25/2019