| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
3 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
2-200AMP |
| D. 3 Phase Over 225 AMPS |
1 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER MECH.RM: BREAKER TIES MISSING FOR MULTIWIRE CKT.. 210.4 |
RSLV |
05/01/2015 |
05/26/2015 |
08/17/2015 |
| |
| 002 |
(999) |
OTHER PANEL: BRANCH CKTS NOT PROPERLY DERATED.. 310.15(B)2A |
RSLV |
05/01/2015 |
05/01/2015 |
05/26/2015 |
| |
| 003 |
(999) |
OTHER TRANSFORMER: GROUNDING ELECTRODE FOR TRANSFORMER NOT BONDED PROPERLY250.26,250.30 |
RSLV |
05/01/2015 |
05/26/2015 |
08/17/2015 |
| |
| 004 |
(999) |
OTHER DISCONNECT: FEEDER FOR 277/480 PANEL OVERFUSED.. 240.4DISCO 277/480 EQUIPMENTS NOT BONDED PROPERLY FOR CONCENTRIC KO250.97 |
RSLV |
05/01/2015 |
05/26/2015 |
08/17/2015 |
| |
| 005 |
(999) |
OTHER 1FL: 2 WIRES 1 LUG FOUR XO BOND IN FRM 110.14 |
RSLV |
05/26/2015 |
05/26/2015 |
08/17/2015 |
| |
| 006 |
(999) |
OTHER 1FL: NO SUPPORT FOR LAY IN LIGHTS IN KITCHEN AREA 41.30 |
RSLV |
05/26/2015 |
05/26/2015 |
08/17/2015 |
| |
| 007 |
(999) |
OTHER 1FL: ALL 480/272V DISCONNECT NEED BONDING 250.97 |
RSLV |
05/26/2015 |
05/26/2015 |
08/17/2015 |
| |
| 008 |
(999) |
OTHER PRIMARY FEED FOR XFRM CONNECTOR NOT MAKING CONECT WITH STEEL 30.10 |
RSLV |
05/26/2015 |
05/26/2015 |
08/17/2015 |
| |
| 009 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 1FL: 12OV CKT GFCI PROTECTED IN KITCHEN 210.8 |
RSLV |
05/26/2015 |
05/26/2015 |
08/17/2015 |
| |
| 010 |
( 29) |
OUTLET BOXES ARE NOT COVERED 1FL: ISOLATED RECEPTICLES NOT BONDED 250.146 |
RSLV |
05/26/2015 |
05/26/2015 |
08/17/2015 |
| |
| 011 |
(999) |
OTHER BSMT: XFRM GRND NONE TO STEEL OR WATER 250.30 XFRM XFRM GRND NOTCONTINOUS 25.64 |
RSLV |
05/26/2015 |
05/26/2015 |
08/17/2015 |