BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M362664
Premises: 179 MADISON AVENUE MANHATTAN BIN: 1017090     Block: 863   Lot: 62
   
Application Completed and Certified

Filed: 179 MADISON AV Census Tract:   74
N/A Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10016 Community Board:   105
Special Place Name:   TINA'S CUBAN CUISINE
DOB Cross Street(s):   EAST 33 STREET,    EAST 34 STREET
Status:   C - JOB IS SIGNED OFF 04/13/2015
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/14/2015 Job Start Date:   12/20/2014
Last Change:   04/13/2015 Job End Date:   02/14/2015
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     04/06/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011324 Licensee Name: JONG HYUN KIM
Firm: 002729 Firm Name: JONG HYUN KIM
Firm Phone: 718-939-8778  Firm Address: 150-13 NORTHERN BLVD FLUSHING NY 11354 

Work Started or Filed by Others: NO
Work Category:   S - SHOP INSPECTION Work To Be Done:   Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: SAIED SOLEIMANI
Owner Business Name: 179 MADISON AVE REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

Sign Dimensions : 12 Ft 0 In  BY  2 Ft 10 In  Total Sq. Ft. of Sign: 34
Sign Type : A
Total Circuits: 1 Total Lamps: 140
Watts (Lamps): 1 Number of Trans: 2 VA of Each Trans: 90
Total Watts or VA: 180 A.W. Gauge of Wire: 16 No. of Sockets Per Circuit: 0
Material/Gauge: 040 AL AND 3/16" PLEXIGLASS
Sign Maker : DK SIGN INC
Sign Maker Address: 25-20 BQE WEST, WOODSIDE, NEW YORK 11377
Shop Address:
Shop Phone:
Shop Location Comments:
Sign Text: TINA'S CUBAN CUISINE

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/22/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ILLIMINATED CHANNEL LETTERS "TINA'S CUBAN CUISINE"

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M362664
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/16/2015 01/22/2015 TSO A (10) (5) Y
INSPECTION COMMENTS: VIOLATIONS. SIGN W/ NOT BACK USED IN WET LOCATION
 
(2) 04/06/2015 04/13/2015 TSO C R (1) (0) Y
INSPECTION COMMENTS: CERTIFICATE IN OFFICE

OBJECTION FOR APPLICATION #: M362664
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
AC CABLE USED IN SIGN W/NO BACK 320.12
RSLV 01/16/2015 01/16/2015 04/06/2015
 
002 (999) OTHER
NO CONNECTORS ON AC CABLE 320.40
RSLV 01/16/2015 01/16/2015 04/06/2015
 
003 (999) OTHER
AC CABLE NOT GROUNDED 250.118
RSLV 01/16/2015 01/16/2015 04/06/2015
 
004 (999) OTHER
POWER SUPPLY NOT LISTED WET LOCATION 110.3
RSLV 01/16/2015 01/16/2015 04/06/2015
 
005 (999) OTHER
SIGN NOT LISTED WATER TIGHT 600.9
RSLV 01/16/2015 01/16/2015 04/06/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order