Electrical Application Details for App #: M362532
Premises: 1125 1 AVENUE MANHATTAN BIN: 1072390     Block: 1436   Lot: 7502
   
Application Completed and Certified

Filed: 350 E 62 ST Census Tract:   110 Health Area:  4900
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
Special Place Name:   THE BEEKMAN
DOB Cross Street(s):   PEDESTRIAN AND BIKE PATH LINK,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 07/08/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/12/2015 10:52 AM
Application Entered:   01/12/2015 Job Start Date:   01/13/2015
Last Change:   07/08/2015 Job End Date:   01/20/2015
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     07/01/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011846 Licensee Name: WINSTON JOHN
Firm: 001795 Firm Name: HEAT-TIMER SERVICE CORP
Firm Phone: 212-481-2020  Firm Address: 79 ALEXANDER AVE STE 36-A BRONX NY 10454 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $239.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MITCH MAYER
Owner Business Name: DOUGLAS ELLIMAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4#6 AWG- 1#8 FROM BR-PP
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  BR-PP 30 CKT AND B-PP
D. 3 Phase Over 225 AMPS  1  1 MMG BURNER
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    11    11  18         
Buildings Total 11    11     18           
Total Units : 47 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/18/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M362532
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/09/2015 02/18/2015 PHG A (25) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 07/01/2015 07/08/2015 PHG C R (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M362532
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT: #6 WIRE ON 70 AMP BREAKER
RSLV 02/09/2015 02/09/2015 07/01/2015
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT: #12 WIRE ON 25 AMP BREAKER 2 TIMES
RSLV 02/09/2015 02/09/2015 07/01/2015
 
003 (999) OTHER
BSMT: EM LIGHT HUNG FROM PLUMBING PIPE.. 110.2,410.30
RSLV 02/09/2015 02/09/2015 07/01/2015