| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER SUB: METAL WIREWAY NOT GROUNDED T-OUT FMC.. 250.118 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 002 |
(999) |
OTHER SUB: NO G.F.I.PROVIDED FOR WATER FOUNTAIN.. 422.52 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 003 |
(999) |
OTHER SUB: ALL BOXES SET BACK MORE THAN 1/4".. 314.20 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 004 |
(999) |
OTHER SUB: NO BOND TO BOX M.C.CABLE WITH ZIPPIES.. 250.8 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 005 |
(999) |
OTHER CEL: NO BOND TO BOX M.C.CABLE IN CEILING T-OUT.. 250.148 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 006 |
(999) |
OTHER CEL: NO BOND TO BOX FOR RECEPTACLES T-OUT.. 250.148 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 007 |
(999) |
OTHER CEL: NO G.F.I.FOR WATER FOUNTAIN.. 422.52 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 008 |
(999) |
OTHER CEL: AHUC2-3,AHUC2-2,AHUC2-1 ALL OVER FUSED.. 110.3 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 009 |
(999) |
OTHER LAUNDRY: NO G.F.I.PROVIDED WITHIN 6' OF SINK.. 210.8 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 010 |
(999) |
OTHER MAIL RM: NO ZIPPIES FOR BOND TO BOX.. 250.8 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 011 |
(999) |
OTHER STUDENT LNG: BOXES SET BACK MORE THAN 1/4" WITH WALL FABRIC T-OUT314.20 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 012 |
(999) |
OTHER FITNESS: LIGHT FIXTURES ARE NOT SUPPORTED.. 410.36 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |
| |
| 013 |
(999) |
OTHER FITNESS: K.O.NOT CLOSED IN PANEL.. 110.2 |
RSLV |
09/02/2015 |
09/02/2015 |
09/30/2015 |