BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M362432
Premises: 65 5 AVENUE MANHATTAN BIN: 1088879     Block: 571   Lot: 1
   
Application Completed and Certified

Filed: 65 5 AV Census Tract:   61 Health Area:  5700
C1, C2 JOB#9380 Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Special Place Name:   THE NEW SCHOOL
DOB Cross Street(s):   EAST 13 STREET,    EAST 14 STREET
Status:   C - JOB IS SIGNED OFF 10/07/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/07/2015 4:44 PM
Application Entered:   01/07/2015 Job Start Date:   01/07/2015
Last Change:   10/07/2015 Job End Date:   02/28/2015
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     09/30/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010613 Licensee Name: ROBERT LIPIRO
Firm: 000553 Firm Name: FRED GELLER ELEC'L INC.
Firm Phone: 718-350-3900  Firm Address: 54-15 38TH AVENUE WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $220.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LIA GARTNEER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SUB    70  37      70         
CEL    236  57      259         
Buildings Total 306  94      329              
Total Units : 732 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/09/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FLOOD REPAIR AT THE NEW SCHOOL JOB# 9380

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M362432
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/02/2015 09/09/2015 ECH A (60) (13) Y
INSPECTION COMMENTS: NONE
 
(2) 09/30/2015 10/07/2015 ECH C R (150) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M362432
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
SUB: METAL WIREWAY NOT GROUNDED T-OUT FMC.. 250.118
RSLV 09/02/2015 09/02/2015 09/30/2015
 
002 (999) OTHER
SUB: NO G.F.I.PROVIDED FOR WATER FOUNTAIN.. 422.52
RSLV 09/02/2015 09/02/2015 09/30/2015
 
003 (999) OTHER
SUB: ALL BOXES SET BACK MORE THAN 1/4".. 314.20
RSLV 09/02/2015 09/02/2015 09/30/2015
 
004 (999) OTHER
SUB: NO BOND TO BOX M.C.CABLE WITH ZIPPIES.. 250.8
RSLV 09/02/2015 09/02/2015 09/30/2015
 
005 (999) OTHER
CEL: NO BOND TO BOX M.C.CABLE IN CEILING T-OUT.. 250.148
RSLV 09/02/2015 09/02/2015 09/30/2015
 
006 (999) OTHER
CEL: NO BOND TO BOX FOR RECEPTACLES T-OUT.. 250.148
RSLV 09/02/2015 09/02/2015 09/30/2015
 
007 (999) OTHER
CEL: NO G.F.I.FOR WATER FOUNTAIN.. 422.52
RSLV 09/02/2015 09/02/2015 09/30/2015
 
008 (999) OTHER
CEL: AHUC2-3,AHUC2-2,AHUC2-1 ALL OVER FUSED.. 110.3
RSLV 09/02/2015 09/02/2015 09/30/2015
 
009 (999) OTHER
LAUNDRY: NO G.F.I.PROVIDED WITHIN 6' OF SINK.. 210.8
RSLV 09/02/2015 09/02/2015 09/30/2015
 
010 (999) OTHER
MAIL RM: NO ZIPPIES FOR BOND TO BOX.. 250.8
RSLV 09/02/2015 09/02/2015 09/30/2015
 
011 (999) OTHER
STUDENT LNG: BOXES SET BACK MORE THAN 1/4" WITH WALL FABRIC T-OUT314.20
RSLV 09/02/2015 09/02/2015 09/30/2015
 
012 (999) OTHER
FITNESS: LIGHT FIXTURES ARE NOT SUPPORTED.. 410.36
RSLV 09/02/2015 09/02/2015 09/30/2015
 
013 (999) OTHER
FITNESS: K.O.NOT CLOSED IN PANEL.. 110.2
RSLV 09/02/2015 09/02/2015 09/30/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.