Premises: 1200 FDR DRIVE MANHATTAN BIN: 1088433     Block: 962   Lot: 80
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1200 FDR DR Census Tract:   62
2 Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10016 Community Board:   106
Special Place Name:   NYU-LMU HOSPITAL ENERGY BUILDING
DOB Cross Street(s):   EAST 30 STREET,    EAST 34 STREET
Status:   C - JOB IS SIGNED OFF 02/22/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/23/2014 Job Start Date:   10/10/2012
Last Change:   02/22/2017 Job End Date:   10/31/2014
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     02/22/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010613 Licensee Name: ROBERT LIPIRO
Firm: 000553 Firm Name: FRED GELLER ELEC'L INC.
Firm Phone: 718-350-3900  Firm Address: 54-15 38TH AVENUE WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $2,187.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52231     Submittal #: 13A0087  
Owner / Occup: RICHARD COHEN
Owner Business Name: NYU HOSPITAL CENTER
Authorized Representative:  RICHARD COHEN
Relationship To Owner:   VICE PRESIDENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  13.2 KVA SW (DOUBLE END)
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  SETS 3-500MCM (13.2)
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003                      5000 
Buildings Total                        5000 
Total Units : 5000 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 06/24/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NYU ENERGY BUILDING JOB #9430CORE BUILDING WORK PERFORMED UNDER APPL # M332965

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M362092
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/30/2015 04/06/2015 GYM V (130) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 06/15/2015 06/24/2015 GYM H X (10) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 02/22/2017 02/22/2017 MQY C R (113) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M362092
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)BSMT 2 4000 AMP,2 AMP GFPE IS REQUIRED FOR EQUIPMENT SUPPLIED BYTRANSFORMER SECONDARY.. ART.215.10
RSLV 03/30/2015 06/15/2015 02/22/2017
 
002 (999) OTHER
(ALL FLOORS) A) BSMT: PANIC BARS MISSING DOORS.. ART.110.26
RSLV 03/30/2015 06/15/2015 02/22/2017
 
003 (999) OTHER
(ALL FLOORS)B) BSMT: NEUTRAL BOND NOT ON LINE SIDE OF THE DISCONNECT LINKART.408.3
RSLV 03/30/2015 06/15/2015 02/22/2017
 
004 (999) OTHER
(ALL FLOORS)C) BSMT: 1000 KVA IS NOT INSTALLED AS PER DRAWING.. 110.2BREAKERS PARALLELING SWER
RSLV 03/30/2015 06/15/2015 02/22/2017
 
005 (999) OTHER
(ALL FLOORS)D) BSMT: 100 AMP FIRE ALARM NO NEUTRAL PROVIDED.. ART.250.24
RSLV 03/30/2015 06/15/2015 02/22/2017