BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M361912
Premises: 372 BROADWAY MANHATTAN BIN: 1001865     Block: 172   Lot: 7505
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 372 BROADWAY Census Tract:   31 Health Area:  7700
ENTIRE BUILDG. Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   FRANKLIN STREET,    WHITE STREET
Status:   C - JOB IS SIGNED OFF 12/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/17/2014 1:14 PM
Application Entered:   12/17/2014 Job Start Date:   12/20/2014
Last Change:   12/14/2017 Job End Date:   12/20/2015
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     12/13/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011464 Licensee Name: THOMAS E JOCELYN III
Firm: 001324 Firm Name: SCIENTIFIC ELEC. CO. INC
Firm Phone: 718-320-2023  Firm Address: 1475 EAST 222ND STREET BRONX NY 10469 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $2,395.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121519589
Building Used As:   Z - Commercial/Residential (1  Stores, 6 Apartments)
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION L - FIRE ALARM LOCAL LAW #5
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARGARET MARTIN
Owner Business Name: MARTIN GROUP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  30 AMP SER. SW.
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  4  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  8  FEEDERS
D. Over 250 MCM  7  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  PANELS
D. 3 Phase Over 225 AMPS  1  400 AMP PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  2  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SUB    30  35    10  30  12  65         
CEL  30  35    10  30  15         
SWL    36        36             
001    12    12  10         
002  30  35    10  30         
003  30  35    10  30         
004  30  35    10  30         
005  30  35    10  30         
006  30  35    10  30         
ROF    12    15  75         
Buildings Total 270  251    75  266     200           
Total Units : 1062 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 6 #10-Wire 3
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/17/2014 Notice: 1 - FIRST NOTICE 09/20/2017
Power Issued: 12/17/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING FOR LIGHTS, HVAC AND POWER FOR TWO NEW ELEVATORSPOWER WIRING ONLY FOR ELEVATOR TO BE COMPLETED UNDER THISPERMIT. ALL CONTROLS AND WIRING FOR OPERATION OF ELEVATOR TOBE DONE BY OTHERS AND IS NOT PART OF THIS PERMIT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M361912
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/19/2017 09/20/2017 GYM V (275) (14)
INSPECTION COMMENTS: ADD PANELS, FEEDERS,
 
(2) 10/26/2017 10/27/2017 CBK J Y (90) (0)
INSPECTION COMMENTS: OBJECTIONS PARTIALLY REMOVED.
 
(3) 12/13/2017 12/14/2017 TOR C R (105) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M361912
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 006) KITCHEN
RSLV 09/19/2017 09/19/2017 10/26/2017
 
002 (999) OTHER
(FLOOR: 008) WHIRLPOOL TUB MOTOR BE ACCESSIBLE 680.73
RSLV 09/19/2017 09/19/2017 10/26/2017
 
003 (999) OTHER
(FLOOR: 008) WHIRLPOOL TUB NO GFCI PROVIDED 680.71
RSLV 09/19/2017 09/19/2017 10/26/2017
 
004 (999) OTHER
(FLOOR: 008)WHIRLPOOL TUB NO BONDING JUMPER METAL WATER SUPPLY 680.74 (PENTHOUSE A )
RSLV 09/19/2017 09/19/2017 12/13/2017
 
005 (999) OTHER
(ALL FLOORS) RECEPTACLES OUTLETS MISSING PENT HOUSE A 210.52
RSLV 09/19/2017 09/19/2017 10/26/2017
 
006 (999) OTHER
(ALL FLOORS)KITCHENS & BATH ROOMS OUTLET BOXES EXTENDERS MISSING 314.20
RSLV 09/19/2017 09/19/2017 10/26/2017
 
007 (999) OTHER
(ALL FLOORS) MC CABLE NOT ALL METAL BOXES ARE BONDED 250.146
RSLV 09/19/2017 09/19/2017 12/13/2017
 
008 (999) OTHER
(ALL FLOORS)AFCI REQUIRED ALL 15 AMP & 20 AMP NEW BRANCH CIRCUITS 210.12
RSLV 09/19/2017 09/19/2017 12/13/2017
 
009 (999) OTHER
(ALL FLOORS) PANELS NEUTRAL BOND NOT REQUIRED 250.24
RSLV 09/19/2017 09/19/2017 12/13/2017
 
010 (999) OTHER
(BASEMENT) FIRE PUMP SHELL BE MARKED FIRE PUMP DO NOT DISC. 695.4
RSLV 09/19/2017 09/19/2017 10/26/2017
 
011 (999) OTHER
(BASEMENT)FIRE PUMP SER. SW. SHELL BE REMOTE 12 " FROM OTHER SER. SW. 695.4
RSLV 09/19/2017 09/19/2017 10/26/2017
 
012 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ROOF) PANEL BLANKS
RSLV 09/19/2017 09/19/2017 10/26/2017
 
013 (999) OTHER
(ROOF) CONDUITS NOT SUPPORTED 358.30
RSLV 09/19/2017 09/19/2017 10/26/2017
 
014 (999) OTHER
(ROOF) OUTLET BOXES NOT SECURED 314.23
RSLV 09/19/2017 09/19/2017 10/26/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.