| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
30 AMP SER. SW. |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
4 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
8 |
FEEDERS |
| D. Over 250 MCM |
7 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
PANELS |
| D. 3 Phase Over 225 AMPS |
1 |
400 AMP PANEL |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
2 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (FLOOR: 006) KITCHEN |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |
| |
| 002 |
(999) |
OTHER (FLOOR: 008) WHIRLPOOL TUB MOTOR BE ACCESSIBLE 680.73 |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |
| |
| 003 |
(999) |
OTHER (FLOOR: 008) WHIRLPOOL TUB NO GFCI PROVIDED 680.71 |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |
| |
| 004 |
(999) |
OTHER (FLOOR: 008)WHIRLPOOL TUB NO BONDING JUMPER METAL WATER SUPPLY 680.74 (PENTHOUSE A ) |
RSLV |
09/19/2017 |
09/19/2017 |
12/13/2017 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS) RECEPTACLES OUTLETS MISSING PENT HOUSE A 210.52 |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS)KITCHENS & BATH ROOMS OUTLET BOXES EXTENDERS MISSING 314.20 |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) MC CABLE NOT ALL METAL BOXES ARE BONDED 250.146 |
RSLV |
09/19/2017 |
09/19/2017 |
12/13/2017 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS)AFCI REQUIRED ALL 15 AMP & 20 AMP NEW BRANCH CIRCUITS 210.12 |
RSLV |
09/19/2017 |
09/19/2017 |
12/13/2017 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS) PANELS NEUTRAL BOND NOT REQUIRED 250.24 |
RSLV |
09/19/2017 |
09/19/2017 |
12/13/2017 |
| |
| 010 |
(999) |
OTHER (BASEMENT) FIRE PUMP SHELL BE MARKED FIRE PUMP DO NOT DISC. 695.4 |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |
| |
| 011 |
(999) |
OTHER (BASEMENT)FIRE PUMP SER. SW. SHELL BE REMOTE 12 " FROM OTHER SER. SW. 695.4 |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |
| |
| 012 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ROOF) PANEL BLANKS |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |
| |
| 013 |
(999) |
OTHER (ROOF) CONDUITS NOT SUPPORTED 358.30 |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |
| |
| 014 |
(999) |
OTHER (ROOF) OUTLET BOXES NOT SECURED 314.23 |
RSLV |
09/19/2017 |
09/19/2017 |
10/26/2017 |