| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
1-400A, 1-600A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
26 |
26-#2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
2-4/0 |
| D. Over 250 MCM |
3 |
2-500, 1-600 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
26 |
26-100A |
| C. 3 Phase Up to 225 AMPS |
2 |
2-200A |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(283) |
SMALL APPLIANCE OUTLETS NOT PROPERLY LOCATED (FLOOR: 001)210.52(C)(5) TH APARTMENTS NOT ALL COUNTER SPACES IS MISSING GFCIRECEPTACLES 2FT/4FT RULE |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 002 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 001)210.52 HABITABLE ROOM WALL SPACES IN TH APARTMENTS MISSINGCONVENIENCE OUTLETS ACCORDING TO 6FT/12FT RULE |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 003 |
(999) |
OTHER (FLOOR: 004)NOTE 3: APT 4A WILL BE ON SEPERATE APP BY CSM AND 4 F NOT LISTED ONANY APP NO WORK TH4 BASEMENT BATHROOM IN PROGRESS |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 004 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ALL FLOORS)240.3 ALL AC BLOWERS AND CONDENSERS THRU OUT OVER FUSED THRU OUT ANDROOF FANS |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 005 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (ALL FLOORS)400.8 ALL HOOD VENTS WIRED WITH ZIP CORD HOOD NOT LISTED FOR THISTYPE OF CONNECTION AND NOT APPROVED FOR NYC |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 006 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS)408.4 ALL PANELS IN THE BUILDING FROM THE ROOF TO THE CELLAR MISSINGDIRECTORIES |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 007 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS)210.8 KITCHEN COUNTERS AND ISLANDS NOT ALL OUTLETS ARE GFCIPROTECTED |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 008 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS)210.8 ALL MEDICINE CABINET OUTLETS ARE NOT GFCI PROTECTED AND NOT TRTYPE RECEPTACLES |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 009 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS)210.12 ALL PANELS THRUOUT MISSING CAFCI BREAKERS FOR ALL LISTED INARTICLE PROVIDED |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS)110.21, 22 ALL EQUIPMENT (PANELS, METERS, DISCONNECTS, SERVICE MUSTHAVE DURABLE LABLING FOR SOURCE AND LOCATION OF OCP ,AND LOAD TO BESERVED FROM CELLAR TO ROOF ALL FLOORS |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS)NOTE 2: CONTRACTOR MUST CONFIRM ALL GROUNDING THRU OUT OF ALLDEVICES |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 012 |
(999) |
OTHER (ALL FLOORS)NOTE 1: ALL OBJECTIONS ARE FOR ALL APTS AND BUILDING THROUGH OUT |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 013 |
(999) |
OTHER (ALL FLOORS)406.11 NOT ALL OUTLETS THRU OUT ARE TR TYPE GFCI AND OR CONVENIENCERECEPTACLES |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 014 |
(999) |
OTHER (ALL FLOORS)110.12, 314.25 ASSORTED KO SEALS AND COVER PLATES MISSING THROUGHOUT |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 015 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT)110.2 DEFECTIVE WIRING IN 800AMP SWITCH POTENTIAL FOR DANGEROUSSITUATION 500MCM UNGROUNDED CONDUCTOR PINCHED AGAINST THE NEUTRALLUG CAUSING DAMAGE TO WIRE |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 016 |
( 2) |
ELECTRIC SIGN HAS BEEN INSTALLED PRIOR TO INSPECTION (BASEMENT)110.2 SIGNAGE NOT PROVIDED FOR ELECTRICAL ROOM DOOR DURABLE MATERIAL |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 017 |
(999) |
OTHER (BASEMENT)110.16 ALL COMMERCIAL EQUIPMENT MUST HAVE ARCH FLASH LABELS |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 018 |
(999) |
OTHER (BASEMENT)110.14 DOUBLE LUGGING OF TERMINALS IN PLP PANEL AND ON BREAKERS INSAME |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 019 |
(999) |
OTHER (BASEMENT)320.12 GAS ROOM BX CABLE AND WIRING SURFACE MOUNTED IN GAS METERROOM NO PROTECTION FROM PHYSICAL DAMAGE |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 020 |
(999) |
OTHER (BASEMENT)110.2 PVC CONDUIT FROM THE END LINE TO THE SERVICE SWITCH IS UNFUSEDAND EXPOSED WHEN LEAVES CONCRETE BOTH ENDS RECOMMEND ENCASEMNT FORPROTECTION 230.6 |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 021 |
(999) |
OTHER (BASEMENT) 110.21,22 110.26 ,110.13 SERVICE END LINE BOX IS MOUNTEDIN HABITABLE AREA OF DUPLEX APT AND ENCLOSED IN WOODEN CABINET (MUSTKEEP PROPER CLEARANCES, VENTILATION IF REQUIRED, AND MUST BE LABELEDON EQUIPMENT COVERS AND IN SIGN IN ELECTRICAL ROOM MUST BE PROVIDED) RECOMMEND GET APPROVAL OF DOB ENGINEER FOR THE LOCATION |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 022 |
(999) |
OTHER (BASEMENT)250.66 GROUNDING FOR 500MCM IN PVC CONDUITS FROM END LINE TO SERVICESWITCHES REQUIRED SIZE ACCORDINGLY TO CODE WHEN USING PVC AND WIRESIZE |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 023 |
(999) |
OTHER (GROUND FLOOR)320.12 , 110.2 WIRING FOR GROUND FLOOR LIGHTING EMBEDDED IN CONCRETEBY THE GROUND FLOOR AC COMPRESSORS |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 024 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (ROOF)250.24(A)(5) NEUTRAL BONDED MBJ IN ROOF AC PANEL 2 X ALSO BONDEDWITH MIXED GROUNDED AND GROUNDING CONDUCTORS |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |
| |
| 025 |
(999) |
OTHER (ROOF) 110.26 ROOF ELECTRICAL CLOSET NO LIGHT PROVIDED |
RSLV |
02/22/2018 |
02/22/2018 |
05/09/2018 |