Electrical Application Details for App #: M361547
Premises: 44 EAST END AVENUE MANHATTAN BIN: 1051138     Block: 1578   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 44 E END AV Census Tract:   136 Health Area:  3800
CELLAR, 1 TO 5 FL Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   EAST 81 STREET,    EAST 82 STREET
Status:   C - JOB IS SIGNED OFF 07/27/2018 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/05/2014 7:17 PM
Application Entered:   12/05/2014 Job Start Date:   12/05/2014
Last Change:   07/27/2018 Job End Date:   12/30/2016
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     05/09/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012245 Licensee Name: PETER ARANA
Firm: 003988 Firm Name: SANT-TEC ELECTRIC INC
Firm Phone: 718-644-7645  Firm Address: 516 INDUSTRIAL LOOP 2ND FL STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
T - TEMPORARY LIGHT & POWER
Total Fee:  $2,300.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121971161
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAVIER BART
Owner Business Name: 44 EAST END LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  1-400A, 1-600A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  26  26-#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  2-4/0
D. Over 250 MCM  3  2-500, 1-600
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  26  26-100A
C. 3 Phase Up to 225 AMPS  2  2-200A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    44  50    30  44  15         
002    32  68    32  68  12         
003    32  68    32  68  12         
004    32  68    32  68  12         
005    32  68    32  68  12         
ROF              12  60         
Buildings Total 172  322    158  316     123           
Total Units : 1091 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 26 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 27 - Removed Meters 0 = Total Meters 27

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/05/2014 Notice: 1 - FIRST NOTICE 02/26/2018
Power Issued: 12/05/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M361547
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/22/2018 02/26/2018 TUR V (20) (25)
INSPECTION COMMENTS: OBJECTIONS ISSUED , SEE APPLICATION M00004133I1EL IN DOB NOW OPENED BY CSM TO CORRECT ALL OBJECTIONS ON THIS APPLICATION AND TO SUPERSEDE THIS APP (THIS APP DOES NOT COVER APTS 4A, IN PROGRESS SEPARATE APP AND 4F NO WORK )
 
(2) 05/09/2018 05/09/2018 VTC C R (37) (0)
INSPECTION COMMENTS: PASS SEE M00004133 AND M00041508

OBJECTION FOR APPLICATION #: M361547
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (283) SMALL APPLIANCE OUTLETS NOT PROPERLY LOCATED
(FLOOR: 001)210.52(C)(5) TH APARTMENTS NOT ALL COUNTER SPACES IS MISSING GFCIRECEPTACLES 2FT/4FT RULE
RSLV 02/22/2018 02/22/2018 05/09/2018
 
002 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(FLOOR: 001)210.52 HABITABLE ROOM WALL SPACES IN TH APARTMENTS MISSINGCONVENIENCE OUTLETS ACCORDING TO 6FT/12FT RULE
RSLV 02/22/2018 02/22/2018 05/09/2018
 
003 (999) OTHER
(FLOOR: 004)NOTE 3: APT 4A WILL BE ON SEPERATE APP BY CSM AND 4 F NOT LISTED ONANY APP NO WORK TH4 BASEMENT BATHROOM IN PROGRESS
RSLV 02/22/2018 02/22/2018 05/09/2018
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS)240.3 ALL AC BLOWERS AND CONDENSERS THRU OUT OVER FUSED THRU OUT ANDROOF FANS
RSLV 02/22/2018 02/22/2018 05/09/2018
 
005 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(ALL FLOORS)400.8 ALL HOOD VENTS WIRED WITH ZIP CORD HOOD NOT LISTED FOR THISTYPE OF CONNECTION AND NOT APPROVED FOR NYC
RSLV 02/22/2018 02/22/2018 05/09/2018
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS)408.4 ALL PANELS IN THE BUILDING FROM THE ROOF TO THE CELLAR MISSINGDIRECTORIES
RSLV 02/22/2018 02/22/2018 05/09/2018
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS)210.8 KITCHEN COUNTERS AND ISLANDS NOT ALL OUTLETS ARE GFCIPROTECTED
RSLV 02/22/2018 02/22/2018 05/09/2018
 
008 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS)210.8 ALL MEDICINE CABINET OUTLETS ARE NOT GFCI PROTECTED AND NOT TRTYPE RECEPTACLES
RSLV 02/22/2018 02/22/2018 05/09/2018
 
009 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS)210.12 ALL PANELS THRUOUT MISSING CAFCI BREAKERS FOR ALL LISTED INARTICLE PROVIDED
RSLV 02/22/2018 02/22/2018 05/09/2018
 
010 (999) OTHER
(ALL FLOORS)110.21, 22 ALL EQUIPMENT (PANELS, METERS, DISCONNECTS, SERVICE MUSTHAVE DURABLE LABLING FOR SOURCE AND LOCATION OF OCP ,AND LOAD TO BESERVED FROM CELLAR TO ROOF ALL FLOORS
RSLV 02/22/2018 02/22/2018 05/09/2018
 
011 (999) OTHER
(ALL FLOORS)NOTE 2: CONTRACTOR MUST CONFIRM ALL GROUNDING THRU OUT OF ALLDEVICES
RSLV 02/22/2018 02/22/2018 05/09/2018
 
012 (999) OTHER
(ALL FLOORS)NOTE 1: ALL OBJECTIONS ARE FOR ALL APTS AND BUILDING THROUGH OUT
RSLV 02/22/2018 02/22/2018 05/09/2018
 
013 (999) OTHER
(ALL FLOORS)406.11 NOT ALL OUTLETS THRU OUT ARE TR TYPE GFCI AND OR CONVENIENCERECEPTACLES
RSLV 02/22/2018 02/22/2018 05/09/2018
 
014 (999) OTHER
(ALL FLOORS)110.12, 314.25 ASSORTED KO SEALS AND COVER PLATES MISSING THROUGHOUT
RSLV 02/22/2018 02/22/2018 05/09/2018
 
015 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT)110.2 DEFECTIVE WIRING IN 800AMP SWITCH POTENTIAL FOR DANGEROUSSITUATION 500MCM UNGROUNDED CONDUCTOR PINCHED AGAINST THE NEUTRALLUG CAUSING DAMAGE TO WIRE
RSLV 02/22/2018 02/22/2018 05/09/2018
 
016 ( 2) ELECTRIC SIGN HAS BEEN INSTALLED PRIOR TO INSPECTION
(BASEMENT)110.2 SIGNAGE NOT PROVIDED FOR ELECTRICAL ROOM DOOR DURABLE MATERIAL
RSLV 02/22/2018 02/22/2018 05/09/2018
 
017 (999) OTHER
(BASEMENT)110.16 ALL COMMERCIAL EQUIPMENT MUST HAVE ARCH FLASH LABELS
RSLV 02/22/2018 02/22/2018 05/09/2018
 
018 (999) OTHER
(BASEMENT)110.14 DOUBLE LUGGING OF TERMINALS IN PLP PANEL AND ON BREAKERS INSAME
RSLV 02/22/2018 02/22/2018 05/09/2018
 
019 (999) OTHER
(BASEMENT)320.12 GAS ROOM BX CABLE AND WIRING SURFACE MOUNTED IN GAS METERROOM NO PROTECTION FROM PHYSICAL DAMAGE
RSLV 02/22/2018 02/22/2018 05/09/2018
 
020 (999) OTHER
(BASEMENT)110.2 PVC CONDUIT FROM THE END LINE TO THE SERVICE SWITCH IS UNFUSEDAND EXPOSED WHEN LEAVES CONCRETE BOTH ENDS RECOMMEND ENCASEMNT FORPROTECTION 230.6
RSLV 02/22/2018 02/22/2018 05/09/2018
 
021 (999) OTHER
(BASEMENT) 110.21,22 110.26 ,110.13 SERVICE END LINE BOX IS MOUNTEDIN HABITABLE AREA OF DUPLEX APT AND ENCLOSED IN WOODEN CABINET (MUSTKEEP PROPER CLEARANCES, VENTILATION IF REQUIRED, AND MUST BE LABELEDON EQUIPMENT COVERS AND IN SIGN IN ELECTRICAL ROOM MUST BE PROVIDED) RECOMMEND GET APPROVAL OF DOB ENGINEER FOR THE LOCATION
RSLV 02/22/2018 02/22/2018 05/09/2018
 
022 (999) OTHER
(BASEMENT)250.66 GROUNDING FOR 500MCM IN PVC CONDUITS FROM END LINE TO SERVICESWITCHES REQUIRED SIZE ACCORDINGLY TO CODE WHEN USING PVC AND WIRESIZE
RSLV 02/22/2018 02/22/2018 05/09/2018
 
023 (999) OTHER
(GROUND FLOOR)320.12 , 110.2 WIRING FOR GROUND FLOOR LIGHTING EMBEDDED IN CONCRETEBY THE GROUND FLOOR AC COMPRESSORS
RSLV 02/22/2018 02/22/2018 05/09/2018
 
024 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(ROOF)250.24(A)(5) NEUTRAL BONDED MBJ IN ROOF AC PANEL 2 X ALSO BONDEDWITH MIXED GROUNDED AND GROUNDING CONDUCTORS
RSLV 02/22/2018 02/22/2018 05/09/2018
 
025 (999) OTHER
(ROOF) 110.26 ROOF ELECTRICAL CLOSET NO LIGHT PROVIDED
RSLV 02/22/2018 02/22/2018 05/09/2018