Electrical Application Details for App #: M361465
Premises: 11 WEST 12 STREET MANHATTAN BIN: 1009621     Block: 576   Lot: 48
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 11 W 12 ST Census Tract:   63 Health Area:  5700
ENTIRE HOUSE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 02/25/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/04/2014 2:11 PM
Application Entered:   12/04/2014 Job Start Date:   12/06/2014
Last Change:   02/25/2019 Job End Date:   07/23/2015
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     02/25/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010759 Licensee Name: YOUNG S CHOE
Firm: 001995 Firm Name: Y.S ELECTRIC
Firm Phone: 866-863-4448  Firm Address: 129-09 26TH AVENUE, #103 FLUSHING NY 11354 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $838.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: AUSTIN KELLY
Owner Business Name: REALTY LLC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1X4
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4X#500
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  2  #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  3X200, 2X100
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  25 HP
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  ENTIR  32  120    75  180  25         
Buildings Total 32  120    75  180     25           
Total Units : 432 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/04/2014 Notice: 1 - FIRST NOTICE 09/06/2018
Power Issued: 12/04/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RENOVATION.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M361465
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/06/2018 09/06/2018 EDB V (105) (12)
INSPECTION COMMENTS: INSPECT CELLAR AND BSMT ONLY. SEE ATTACHMENT.
 
(2) 02/25/2019 02/25/2019 JTE C R (50) (0)
INSPECTION COMMENTS: INSPECTION PASS, OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M361465
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)MC CABLE AND FMC NOT PROPERLY GND 250.112,118,122
RSLV 09/06/2018 09/06/2018 02/25/2019
 
002 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
(ALL FLOORS)GREEN WIRE USED AS NEUTRAL AND AS HOT 200.6, 250.119
RSLV 09/06/2018 09/06/2018 02/25/2019
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) SWITCHES AND RECEPTACLE IN COMBUSTIBLE MATERIAL314.20,21
RSLV 09/06/2018 09/06/2018 02/25/2019
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) AFCI PROTECTION NOT PER 210.12
RSLV 09/06/2018 09/06/2018 02/25/2019
 
005 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(BASEMENT)NO ACCESS TO LED DRIVERS 110.26
RSLV 09/06/2018 09/06/2018 02/25/2019
 
006 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(CELLAR) S. SW. NOT BONDED250.24,28
RSLV 09/06/2018 09/06/2018 02/25/2019
 
007 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) NO GND ROD , BUILDING HAS TWO WATER PIPE 250.50,52
RSLV 09/06/2018 09/06/2018 02/25/2019
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) LFNC IN USE AM. 356.10
RSLV 09/06/2018 09/06/2018 02/25/2019
 
009 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR)OVERSIZE WIRES IN 100 A CB 110.2,3
RSLV 09/06/2018 09/06/2018 02/25/2019
 
010 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR)BOILER RM. : MC CONNECTORS NOT APPROVED 110.2,3
RSLV 09/06/2018 09/06/2018 02/25/2019
 
011 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(CELLAR) ROOM RECEPTACLE NOT PER 210.52
RSLV 09/06/2018 09/06/2018 02/25/2019
 
012 (999) OTHER
(CELLAR)NO DISC. MEANS PROVIDED FOR SAUNA 424.19
RSLV 09/06/2018 09/06/2018 02/25/2019