BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M361217
Premises: 14 EXCHANGE PLACE MANHATTAN BIN: 1000830     Block: 27   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 20 EXCHANGE PL Census Tract:   7 Health Area:  7700
10 / 11 Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10005 Community Board:   101
DOB Cross Street(s):   HANOVER STREET,    WILLIAM STREET
Status:   C - JOB IS SIGNED OFF 03/02/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/25/2014 8:16 AM
Application Entered:   11/25/2014 Job Start Date:   11/26/2014
Last Change:   03/02/2016 Job End Date:   12/02/2014
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     03/19/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011451 Licensee Name: ROBERT E SALINGER
Firm: 003205 Firm Name: JOROB CONTR'G & ELEC'L CO
Firm Phone: 212-704-2040  Firm Address: 1040 AVENUE OF THE AMERICAS INC. NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $4,185.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: RBNB 20 OWNER LLC
Authorized Representative:  RICHARD RAMOS
Relationship To Owner:   REPRESNTITIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  64  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  65  24 CIRCUIT 100 AMP
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
010    155  500  30  60  155             
011    155  500  30  60  155             
Buildings Total 310  1000  60  120  310                
Total Units : 1800 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/25/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M361217
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/15/2015 01/22/2015 ECH A (100) (1) Y
INSPECTION COMMENTS: NONE
 
(2) 02/19/2015 02/25/2015 PHG A R (70) (2) Y
INSPECTION COMMENTS: 600 MCM RAN IN PARRELL
 
(3) 03/19/2015 03/27/2015 TOR C R (60) (0) Y
INSPECTION COMMENTS: OBJECTIONS INSPECTED ONLY

OBJECTION FOR APPLICATION #: M361217
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
10 & 11: DIDTRIBUTION BOARDS OVER FUSED 600 MCM ALL ON 800A BREAKERS310.16
RSLV 01/15/2015 01/15/2015 02/19/2015
 
002 ( 40) LOCKNUTS ARE MISSING OR LOOSE
11 FLOOR LOCK NUT MISSING FROM CABLE ON 11 FLOR MDP 2B 300.10
RSLV 02/19/2015 02/19/2015 03/19/2015
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
11 FLOOR GROUND NOT TERMINATED IN AL MDP 11 FLOOR WITH M/C CABLE 250.122
RSLV 02/19/2015 02/19/2015 03/19/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back