BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M360981
Premises: 572 MADISON AVENUE MANHATTAN BIN: 1035778     Block: 1292   Lot: 15
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 590 MADISON AV Census Tract:   112.02 Health Area:  4800
9TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
DOB Cross Street(s):   EAST 56 STREET,    EAST 57 STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 03/25/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/18/2014 5:33 PM
Application Entered:   11/18/2014 Job Start Date:   11/18/2014
Last Change:   03/25/2016 Job End Date:   03/15/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     03/24/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 010487 Licensee Name: CIRO LUPO
Firm: 001787 Firm Name: COMMERCIAL ELECT CONT INC
Firm Phone: 718-784-3500  Firm Address: 10-28 47TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $257.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 590 MADISON AVE. LLC
Authorized Representative:  JOSEPH GREISH
Relationship To Owner:   BUILDING MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  (2) SETS #2; (1) SET #4
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  (2) 3? PANELS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
009    35  71    20  143          30 
Buildings Total 35  71    20  143               30 
Total Units : 299 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 03/25/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  BREVAN HOWARD

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M360981
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/28/2015 02/03/2015 EDB V (55) (1) Y
INSPECTION COMMENTS: CONTRACTOR REP NEVER BEEN ON JOB SITE
 
(2) 04/30/2015 05/06/2015 PHG V X (50) (3) Y
INSPECTION COMMENTS: CONTRACTOR UNAWARE OF WORK DONE FULL INSPECT NEEDED
 
(3) 01/12/2016 01/14/2016 STP V X (35) (1)
INSPECTION COMMENTS: NONE
 
(4) 03/24/2016 03/25/2016 MQY V X (38) (1)
INSPECTION COMMENTS: OBJECTIONS PARTIALLY REMOVED. ISSUED OBJECTION. DID NOT INSPECT GYM

OBJECTION FOR APPLICATION #: M360981
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
9FL: NO ARC FLASH WARNING ON NEW EQUIPMENT.. 110.16
OPEN 01/28/2015 04/30/2015
 
002 (999) OTHER
9 FLOOR NO HANDLE FUSE PROVIDED IN ALL PANEL 210.4
OPEN 04/30/2015 04/30/2015
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
9 FLOOR EMT NOT SUPPORTED IN ELECTRCIAL ROOM A
OPEN 04/30/2015 04/30/2015
 
004 (999) OTHER
9 FLOOR NO HIGH VOLT STIKER PROVIDED 110.16
OPEN 04/30/2015 04/30/2015
 
005 (999) OTHER
(FLOOR: 009) BOX NOT BONDED M.C. CABLE 250.148
OPEN 01/12/2016 01/12/2016
 
006 (999) OTHER
(FLOOR: 009)FLEXIBLE CORD RAN THROUGH SUSPENDED CEILING (FLAT SCREENTELEVISIONS)(400.8)
OPEN 03/24/2016 03/24/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order