BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M360731
Premises: 510 GREENWICH STREET MANHATTAN BIN: 1010348     Block: 595   Lot: 75
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 510 GREENWICH ST Census Tract:   37 Health Area:  6800
BSMT Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   CANAL STREET,    HOLLAND TUNNEL
Status:   C - JOB IS SIGNED OFF 12/30/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/12/2014 6:29 PM
Application Entered:   11/12/2014 Job Start Date:   11/12/2014
Last Change:   12/30/2015 Job End Date:   11/12/2015
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     12/10/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012244 Licensee Name: JEAN PAUL WILLIAMS
Firm: 003639 Firm Name: GOLD STAR ELECT'L, INC
Firm Phone: 718-961-7827  Firm Address: 59-24 57TH STREET MASPETH NY 11378 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
012012 MOUNAS, SAMY A 003639 GOLD STAR ELECT'L, INC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $278.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 1 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLIAM GOTTLIEB
Owner Business Name: GOTTLIEB
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  APT ON 2ND FL.(SINGLE PHA
B. 101 Up to 200 AMPS  1  STORE 3PHASE
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  1  FOUR 350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  125A.... MB SINGLE PHASE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 AMP, MB THREE PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 1 #10-Wire 0
Existing Meters 2 + New Meters 2 - Removed Meters 2 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/12/2014 Notice: 1 - FIRST NOTICE 02/04/2015
Power Issued: 11/12/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M360731
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/23/2015 02/04/2015 NRS V E (50) (5) Y
INSPECTION COMMENTS: 200A SERVICE TEMPED-UP
 
(2) 04/17/2015 04/23/2015 WYF N (30) (0) Y
INSPECTION COMMENTS: CALLLED CONTRACTOR SAID THEY HAD CANCELLED
 
(3) 11/09/2015 11/17/2015 CBK N (35) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(4) 11/24/2015 12/01/2015 EID N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR SHOWED BUT TENANT FOR STORE DID NOT
 
(5) 12/10/2015 12/30/2015 EDB C R (34) (0)
INSPECTION COMMENTS: INSPECT OBJECTION ONLY

OBJECTION FOR APPLICATION #: M360731
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) BASE: BOTH SERVICE PANEL
RSLV 01/23/2015 01/23/2015 12/10/2015
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) BASE: 125A SERVICE/PANEL
RSLV 01/23/2015 01/23/2015 12/10/2015
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ALL FLOORS) BASE: 40A APT FEEDER RUN WITH #2 AWG E.B.I
RSLV 01/23/2015 01/23/2015 12/10/2015
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) BASE
RSLV 01/23/2015 01/23/2015 12/10/2015
 
005 (279) WATER METER JUMPER IS MISSING/IMPROPER
(ALL FLOORS) BASE: 2ND METER
RSLV 01/23/2015 01/23/2015 12/10/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.