BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M360593
Premises: 131 WEST 45 STREET MANHATTAN BIN: 1089796     Block: 998   Lot: 15
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 135 W 45 ST Census Tract:   119
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10036 Community Board:   105
Special Place Name:   TIMES SQUARE HYATT
Related Job Number:    104844180
DOB Cross Street(s):   AVENUE OF THE AMERICAS,    7 AVENUE
Status:   C - JOB IS SIGNED OFF 03/22/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   11/07/2014 Job Start Date:   10/28/2014
Last Change:   03/22/2017 Job End Date:   10/28/2016
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     03/22/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012292 Licensee Name: ANTHONY FIGUCCIO
Firm: 002661 Firm Name: S. J. ELECTRIC INC.
Firm Phone: 718-643-7274  Firm Address: 94-02 LINDEN BLVD OZONE PARK NY 11417 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54325     Submittal #: 16A0944  
Owner / Occup: LOUIS ARZANO
Owner Business Name: EXTELL DEVELOPMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  4  2-2000,1@3000,1@2500,
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  15  12 @ #2, 3 @ #10
B. Over #2 to 1/0  8  
C. Over 1/0 to 250 MCM  10  8 @ 4/0, 2 @ 2/0
D. Over 250 MCM  51  45 @ 500MCM, 6 @ 350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 2 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/07/2014 Notice: 1 - FIRST NOTICE 11/29/2016
Power Issued: 11/07/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ADVISORY BOARD SERVICE ONLYJOB FILED ON APPLICATION # M321749 CAL#52494 REPLACED BY CAL#53060. REQUEST 2/6/17 TO CHANGE CAL # TO 54325 UNDER SUMISSION #16A0944

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M360593
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/24/2014 12/03/2014 BMP A E (80) (1) Y
INSPECTION COMMENTS: SEE FILING DETAILS
 
(2) 06/23/2015 07/06/2015 EDB V X E (165) (0) Y
INSPECTION COMMENTS: NOT FINAL
 
(3) 11/25/2015 11/30/2015 ECH V X E (240) (14) Y
INSPECTION COMMENTS: NEW PRINT #53060. GENERATOR + MSB-4 NOT INSPECTED
 
(4) 10/05/2016 10/06/2016 EDB V X (205) (4)
INSPECTION COMMENTS: NO FIRE PROOF PAPERWORK . JOB NOT PER REV. # 8.
 
(5) 11/28/2016 11/29/2016 EDB V Y (240) (4)
INSPECTION COMMENTS: NO FIRE PROOF PAPERWORK. JOB NOT PER REV. # 8. LOCATION OF GEC FOR GENERATOR IS PROBLEM.
 
(6) 12/23/2016 12/27/2016 TOR J Y (105) (0)
INSPECTION COMMENTS: CONTRACTOR RE -FILE JOB WITH ADVISORY.
 
(7) 02/23/2017 02/24/2017 GYM J R (145) (0)
INSPECTION COMMENTS: CONTRACTOR NEED FILE FOR 4 SERVICE SWITCHES.
 
(8) 03/22/2017 03/22/2017 GYM C (45) (0) Y
INSPECTION COMMENTS: SEE APPL. # M393025

OBJECTION FOR APPLICATION #: M360593
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) BSMT: NOT INSTALLED PER ADVISORY BOARD DRAWINGSSEE DRAWINGS FOR DETAILS
RSLV 11/24/2014 11/25/2015 02/23/2017
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) T-OUT: ALL ATS SWITCHES ARE 4 WIRE
RSLV 11/25/2015 11/25/2015 12/23/2016
 
003 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) SER A: XFMR SEC. SW. -FUSE SIZE
RSLV 11/25/2015 11/25/2015 11/28/2016
 
004 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) SER B: CON ED STEAM SW-SIZE
RSLV 11/25/2015 11/25/2015 12/23/2016
 
005 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) SER B: CON ED STEAM SW- WIRE SIZE
RSLV 11/25/2015 11/25/2015 02/23/2017
 
006 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) SER B: CON ED STEAM SW- GROUNDING + BONDING
RSLV 11/25/2015 11/25/2015 12/23/2016
 
007 (999) OTHER
(ALL FLOORS) SER B: CON ED STEAM SW-NOT GROUNDED OR BONDED 250.24
RSLV 11/25/2015 11/25/2015 12/23/2016
 
008 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) SER B: S.SW B1 -FUSE SIZE
RSLV 11/25/2015 11/25/2015 11/28/2016
 
009 (999) OTHER
(ALL FLOORS) SER B: S.SW B1 -LOAD CONDUCTORS OVER FUSED 310.16
RSLV 11/25/2015 11/25/2015 11/28/2016
 
010 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)SER B: 750 KVA-NEUTRAL BONDED IN TRANSFORMER AND SECONDARY SWITCH
RSLV 11/25/2015 11/25/2015 11/28/2016
 
011 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) SER B: HPP -LGT -MEZZ -OVER FUSED
RSLV 11/25/2015 11/25/2015 11/28/2016
 
012 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) SER B: FEED FOR BPP-CB UNDERSIZED
RSLV 11/25/2015 11/25/2015 11/28/2016
 
013 (999) OTHER
(ALL FLOORS)SER B: NEUTRAL BONDED BEYOND SERVICE BPP-CB DISCONNECT 250.24
RSLV 11/25/2015 11/25/2015 11/28/2016
 
014 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) ATS RM: CELLAR -WIRES SIZE LOAD SIDE 30 KVA FACP
RSLV 11/25/2015 11/25/2015 11/28/2016
 
015 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) ATS RM: CELLAR -WIRE SIZE BETWEEN ATS AND 100A SWITCH
RSLV 11/25/2015 11/25/2015 11/28/2016
 
016 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)SEC. SW. 1600 A (FUSED AT 1200 A) NOT PROPERLY GND 250.30
RSLV 10/05/2016 10/05/2016 11/28/2016
 
017 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR)STEAM S. SW. : 1/0 AWG SERV. ENTER CONDUCTOR , # 8 AWG -- GEC250.66
RSLV 10/05/2016 10/05/2016 11/28/2016
 
018 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(ROOF) GENERATOR NOT PROPERLY GND 250.30
RSLV 10/05/2016 10/05/2016 12/23/2016
 
019 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ROOF) F/A AND F/P : MISSING NEUTRAL AND DIFFERENT FUSES IN USE110.2,3 215.4 B ,300,3 B
RSLV 10/05/2016 10/05/2016 11/28/2016
 
020 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(FLOOR: 055) EL. RM. : EMT NOT SECURED FOR GEC 358.30
RSLV 11/28/2016 11/28/2016 12/23/2016
 
021 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(CELLAR)F/A DISC. SW. TO SEC. OF 3W0 KVA : NO EQUIPMENT GND 250.118
RSLV 11/28/2016 11/28/2016 12/23/2016
 
022 ( 42) BUSHINGS ARE MISSING OR LOOSE
(CELLAR) F/A DISC. SW. : #2 AWG MISSING BUSHING 300.4
RSLV 11/28/2016 11/28/2016 12/23/2016
 
023 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(CELLAR) F/A DISC. SW. TO ATS : EMT NOT SECURED 358.30
RSLV 11/28/2016 11/28/2016 12/23/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back