Electrical Application Details for App #: M360450
Premises: 17 STANTON STREET MANHATTAN BIN: 1087361     Block: 426   Lot: 24
   
Application Completed and Certified

Filed: 17 STANTON ST Census Tract:   36.01 Health Area:  6500
GROUND FL. Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   BOWERY,    CHRYSTIE STREET
Status:   C - JOB IS SIGNED OFF 01/27/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/04/2014 10:39 AM
Application Entered:   11/04/2014 Job Start Date:   11/04/2014
Last Change:   01/27/2015 Job End Date:   03/30/2015
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     01/05/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011915 Licensee Name: MIKHAIL MIKHAYLOV
Firm: 003550 Firm Name: APS ELECTRIC INC
Firm Phone: 718-996-9187  Firm Address: 36-36 33RD STREET, SUITE 205 LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $105.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   C7-WALK-UP APARTME
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ARIEL SOUDRY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND              10         
Buildings Total              10           
Total Units : 10 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/24/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REMOVING DOB VIOLATION ECB #35038326L

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M360450
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/17/2014 11/24/2014 NRS A (50) (13) Y
INSPECTION COMMENTS: NONE
 
(2) 01/05/2015 01/12/2015 WYF C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M360450
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (219) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:RMC)
BACKYARD
RSLV 11/17/2014 11/17/2014 01/05/2015
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
BACK Y: A/H DISCONNECT
RSLV 11/17/2014 11/17/2014 01/05/2015
 
003 (999) OTHER
BACK Y: L.B UNDER AIR HANDLER HAS NO COVER. 314.25
RSLV 11/17/2014 11/17/2014 01/05/2015
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
GROUND: IN BAR NEW PANEL
RSLV 11/17/2014 11/17/2014 01/05/2015
 
005 ( 40) LOCKNUTS ARE MISSING OR LOOSE
GROUND: IN NEW PANEL LOOSE
RSLV 11/17/2014 11/17/2014 01/05/2015
 
006 (999) OTHER
GROUND: NO TIE BREAKER ON MULTIWIRE CIRCUITS. 210.4
RSLV 11/17/2014 11/17/2014 01/05/2015
 
007 (999) OTHER
OUTSIDE: E.G.C.IN A/C DISCONNECT NOT AS PER 250.122
RSLV 11/17/2014 11/17/2014 01/05/2015
 
008 (219) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:RMC)
OUTSIDE: AT A/C COMPRESSORS
RSLV 11/17/2014 11/17/2014 01/05/2015
 
009 ( 19) DEFECTIVE WIRING IS IN USE
OUTSIDE: AT A/C LFMC USED. AM.356.10
RSLV 11/17/2014 11/17/2014 01/05/2015
 
010 (999) OTHER
OUTSIDE: LFMC NOT SUPPORTED AS PER 350.30
RSLV 11/17/2014 11/17/2014 01/05/2015
 
011 (999) OTHER
OUTSIDE: A/C G.F.C.I. HAS NO IN USE COVER. 406.8
RSLV 11/17/2014 11/17/2014 01/05/2015
 
012 (999) OTHER
OUTSIDE: A/C DISCONNECT E.G.C. DOUBLE LUG. 110.14
RSLV 11/17/2014 11/17/2014 01/05/2015
 
013 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTSIDE: AT A/C LIQUID TIGHT FITTINGS
RSLV 11/17/2014 11/17/2014 01/05/2015