Electrical Application Details for App #: M360196
Premises: 281 WEST 11 STREET MANHATTAN BIN: 1011365     Block: 623   Lot: 55
   
Application Completed and Certified

Filed: 281 W 11 ST Census Tract:   77 Health Area:  6100
APT 1AB Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   WEST 4 STREET,    BLEECKER STREET
Status:   C - JOB IS SIGNED OFF 02/19/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/27/2014 8:05 PM
Application Entered:   10/27/2014 Job Start Date:   10/28/2014
Last Change:   02/19/2015 Job End Date:   10/30/2014
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     01/09/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012204 Licensee Name: DRITAN BANUSHI
Firm: 003917 Firm Name: BRUNI ELECTRIC INC
Firm Phone: 718-729-0700  Firm Address: 37-24 24TH STREET STE 128 LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WADE HOLLAND
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1AB                   
Buildings Total                     
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/01/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL 1 NEW GFCI OUTLET IN THE BATHROOM AND NEW LINE FROMPANEL,INSTALL 2 NEW LINE AND OUTLETS IN THE SPACE AND INSTALL 1 NEW LINE 110V AC WINDOW .

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M360196
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/26/2014 12/01/2014 NRS V (50) (9) Y
INSPECTION COMMENTS: JOB NOT FINISHED, (G) NEW CIRCUITS
 
(2) 12/23/2014 12/31/2014 DNM J Y (30) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 01/09/2015 01/20/2015 TOR C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M360196
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
BASEMENT
RSLV 11/26/2014 12/23/2014 01/09/2015
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
BASEMENT WET BAR GFCI BOX
RSLV 11/26/2014 12/23/2014 01/09/2015
 
003 (999) OTHER
BASEMENT WET BAR OUTLET BOXES SET TOO DEEP 314 314.20
RSLV 11/26/2014 12/23/2014 01/09/2015
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BASEMENT SHEET ROCK SCREWS USED FOR DEVICES
RSLV 11/26/2014 12/23/2014 01/09/2015
 
005 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
BASEMENT RECEPTACLES
RSLV 11/26/2014 12/23/2014 01/09/2015
 
006 (999) OTHER
BASEMENT NEW DEDICATED BATH GFCI AND CIRCUIT NOT AS PER 210.11(C)(3)AND 210.21 (B) (1)
RSLV 11/26/2014 12/23/2014 01/09/2015
 
007 ( 19) DEFECTIVE WIRING IS IN USE
BASEMENT A/C RECE DOES NOT WORK
RSLV 11/26/2014 11/26/2014 12/23/2014
 
008 ( 19) DEFECTIVE WIRING IS IN USE
BASEMENT BATH RECE DOES NOT WORK
RSLV 11/26/2014 11/26/2014 12/23/2014
 
009 ( 57) EXPOSED ARMORED CABLES ARE SUBJECT TO PHYSICAL DAMAGE
BASEMENT FOR BEDROOM CIRCUITS
RSLV 11/26/2014 11/26/2014 12/23/2014