BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M359852
Premises: 229 WEST 28 STREET MANHATTAN BIN: 1014255     Block: 778   Lot: 20
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 229 W 28 ST Census Tract:   95 Health Area:  5200
8TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
Related Job Number:    122096230
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/16/2014 4:31 PM
Application Entered:   10/16/2014 Job Start Date:   10/17/2014
Last Change:   08/22/2025 Job End Date:   01/30/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     03/19/2015      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011155 Licensee Name: THOMAS FITZPATRICK
Firm: 002547 Firm Name: TOM FITZPATRICK ELECTRICA
Firm Phone: 718-846-2127  Firm Address: 630 9TH AVENUE STE 207 CONTRACTING CORP NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
T - TEMPORARY LIGHT & POWER
Total Fee:  $120.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122096230
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES DOHERTY
Owner Business Name: LEXINGTON CAPITAL
Authorized Representative:  DOHERTY JAMES
Relationship To Owner:   VP OF DEVELOPMENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  3 PHASE 50 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008    59  55    18  59         
Buildings Total   55    18  59                
Total Units : 132 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/26/2015
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M359852
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/09/2015 03/13/2015 TOR N (15) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR. WAITING FOR RESPONSE. NO SHOW
 
(2) 03/19/2015 03/26/2015 PHG V (60) (10) Y
INSPECTION COMMENTS: A/C WORK NOT DONE YET AS OF 3/19/15 ONLY SPLIT SYSTEM

OBJECTION FOR APPLICATION #: M359852
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
8FL: NO HANDLE TIES PROVIDED FOR MULTI WIRE CKT 210.4
OPEN 03/19/2015 03/19/2015
 
002 (999) OTHER
8FL: GRND WIRES FROM M/C CABLE NOT TERMINATED 250.4
OPEN 03/19/2015 03/19/2015
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
8FL: BREAKER BLANKS MISSING ALL PANEL
OPEN 03/19/2015 03/19/2015
 
004 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
8FL: GRND WIRE ON NEUTRAL BAR 250.24
OPEN 03/19/2015 03/19/2015
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
8FL: KO MISSING IN ALL PANELS
OPEN 03/19/2015 03/19/2015
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
8FL: CFCI NOT PROVIDED IN ALL BATH RMS 210.8
OPEN 03/19/2015 03/19/2015
 
007 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
8FL: RECEPTACLE NOT BONDED M/C CABLE T-OUT 250.146
OPEN 03/19/2015 03/19/2015
 
008 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
8FL: FURNITURE FEED NOT BONDED IN NYC BOX 250.146
OPEN 03/19/2015 03/19/2015
 
009 (999) OTHER
8FL: NO GFCI PROVIDED BY A/C SPLIT SYSTEM 210.63
OPEN 03/19/2015 03/19/2015
 
010 (999) OTHER
8FL: 1 1/4 PIPE NEEDS DERATING 310.15
OPEN 03/19/2015 03/19/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back