BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M359838
Premises: 43 EAST 53 STREET MANHATTAN BIN: 1035731     Block: 1289   Lot: 28
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 45 E 53 ST Census Tract:   102 Health Area:  4800
CELLAR, GROUND Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   BANCO SANTANDER
DOB Cross Street(s):   MADISON AVENUE,    PARK AVENUE
Status:   C - JOB IS SIGNED OFF 04/04/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/16/2014 11:09 AM
Application Entered:   10/16/2014 Job Start Date:   10/16/2014
Last Change:   04/04/2017 Job End Date:   03/15/2015
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     03/10/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011556 Licensee Name: MARIAN BRODNANSKY
Firm: 002191 Firm Name: EGG ELECTRIC INC.
Firm Phone: 212-633-9551  Firm Address: 35 WEST 45TH STREET 4TH NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $127.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: BANCO SANTANDER
Authorized Representative:  MALONEY MARIA
Relationship To Owner:   FILING REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4 #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  100A MCB
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL             
GND    12  15    40      12     
Buildings Total 15  21    46        12      
Total Units : 100 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/16/2014 Notice: 1 - FIRST NOTICE 02/18/2015
Power Issued: 10/16/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  EGG JOB# 2468

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M359838
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/11/2015 02/18/2015 EID A E (65) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 03/10/2017 03/13/2017 CBK C R (45) (0)
INSPECTION COMMENTS: OBJECTION REMOVED.

OBJECTION FOR APPLICATION #: M359838
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)EL CLO 200A SECOND LUL BUS DUCT SW TAPPED OF 200A SSW IN ADVISORYBOARD ROOM (AMD 110 2 (B)
RSLV 02/11/2015 02/11/2015 03/10/2017
 
002 (999) OTHER
(ALL FLOORS) EL CLO BUS DUCT SW DOOR OPENS ONLY 45 (110.26)
RSLV 02/11/2015 02/11/2015 03/10/2017
 
003 (999) OTHER
(ALL FLOORS) BASEMENT PANTRY RECEP SET BACK IN COMBUSTIBLE (314.20)
RSLV 02/11/2015 02/11/2015 03/10/2017
 
004 (999) OTHER
(ALL FLOORS)BASEMENT/1ST FLOOR TAP CONDUCTOR IN 200A BUS DUCT SW IS INSUFFICIENTFOR TAP FROM 2000A SER..SW
RSLV 02/11/2015 02/11/2015 03/10/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back