BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M359660
Premises: 66 EAST 91 STREET MANHATTAN BIN: 1046996     Block: 1502   Lot: 45
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 66 E 91 ST Census Tract:   150.02
ENTIRE BLDG Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
Special Place Name:   RESIDENCE
Related Job Number:    121560765
DOB Cross Street(s):   MADISON AVENUE,    PARK AVENUE
Status:   C - JOB IS SIGNED OFF 01/12/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/10/2014 Job Start Date:   09/10/2014
Last Change:   01/12/2017 Job End Date:   09/05/2015
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     01/09/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012345 Licensee Name: STANISLAW GAJEWSKI
Firm: 004130 Firm Name: STAN ELECTRIC INC
Firm Phone: 212-967-4659  Firm Address: 450 WEST 36TH STREET NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $865.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: MATTHEW SHARP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    35  21    12  35  12         
BAS    47  34    29  47      14     
001    35  25    12  35             
002    36  30    30  36     
003    38  30    30  38         
004    27  26    19  27         
ROF             
Buildings Total 219  168    133  219     29     22      
Total Units : 790 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 2 + New Meters 1 - Removed Meters 2 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/10/2014 Notice: 1 - FIRST NOTICE 12/13/2016
Power Issued: 10/10/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M359660
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/07/2016 12/13/2016 BUR V (100) (5)
INSPECTION COMMENTS: HOUSE BRANCH WIRING
 
(2) 01/09/2017 01/11/2017 MLF C R (27) (0)
INSPECTION COMMENTS: ALL OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M359660
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 005)LIGHT FIXTURE ON UPPER STAIRWAY NOT U.L LISTED AMEN 110.2
RSLV 12/07/2016 12/07/2016 01/09/2017
 
002 (999) OTHER
(CELLAR)EQUIPMENT GROUNDING CONDUCTOR UNDERSISE IN ENDBOX TABLE 250.66
RSLV 12/07/2016 12/07/2016 01/09/2017
 
003 (999) OTHER
(CELLAR) MDP IN CELLAR HAS NO DIRECTORY 408.4
RSLV 12/07/2016 12/07/2016 01/09/2017
 
004 (999) OTHER
(CELLAR) ARC FAULT PROTECTION MISSING ON BRANCH CIRCUITS 210.12
RSLV 12/07/2016 12/07/2016 01/09/2017
 
005 (999) OTHER
(CELLAR) THROUGH OUT HOUSE RECEPTACLES NO T.R TYPE 406.11
RSLV 12/07/2016 12/07/2016 01/09/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back