Premises: 58 SPRING STREET MANHATTAN BIN: 1007197     Block: 481   Lot: 7502
   
Application Completed and Certified

Filed: 225 LAFAYETTE ST Census Tract:   41 Health Area:  6800
2 FL Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   KENMARE STREET,    SPRING STREET
Status:   C - JOB IS SIGNED OFF 12/10/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/08/2014 11:14 PM
Application Entered:   10/08/2014 Job Start Date:   10/08/2014
Last Change:   12/10/2014 Job End Date:   12/02/2014
Appointment Status:   
Last Inspection By:   RIVERA, F       On     11/17/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012079 Licensee Name: DARIUSZ GRYGLEWSKI
Firm: 004264 Firm Name: FSM ELECTRICAL CORPORATIO
Firm Phone: 718-482-9151  Firm Address: 11-20 37TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $44.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHESTER MIERZWINSKI
Owner Business Name: PM CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002      13    14               
Buildings Total   13    14                  
Total Units : 27 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/27/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  KITCHEN RENOVATION, BEDROOM ,BATHROOM ,TWO TOWER RADIATORS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M359552
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/22/2014 10/27/2014 NRS V (50) (9) Y
INSPECTION COMMENTS: NO ACCESS TO KITCHEN LED DRIVER KITCHEN,M.BATH & M.BEDROOM RENOVATED
 
(2) 11/17/2014 12/05/2014 FRI C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M359552
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
2FL: OUTLET BOXES TOO DEEP. 314.20
RSLV 10/22/2014 10/22/2014 11/17/2014
 
002 (999) OTHER
2FL: NO VANITY G.F.C.I.IN M.BATH. 210.52
RSLV 10/22/2014 10/22/2014 11/17/2014
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
2FL: M.BATH TOWEL HEATER SWITCH BOX,MC GROUND WIRE USED AS SWITCHLEG
RSLV 10/22/2014 10/22/2014 11/17/2014
 
004 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
2FL: M.BATH TOWEL HEATER SWITCH BOX
RSLV 10/22/2014 10/22/2014 11/17/2014
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
2FL: DRYER RECE GR.NOT AS PER 250.122
RSLV 10/22/2014 10/22/2014 11/17/2014
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
2FL: (2) TOWEL HEATER IN BATHROOMS
RSLV 10/22/2014 10/22/2014 11/17/2014
 
007 (999) OTHER
2FL: M.BED RECES NOT T/R. 406.11
RSLV 10/22/2014 10/22/2014 11/17/2014
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
2FL: LED DRIVER FOR M.BATH & M.BED CLOSET LIGHTS FED WITH #14 AWGFIRE ALARM CABLE (TYPE FPLP)
RSLV 10/22/2014 10/22/2014 11/17/2014
 
009 (999) OTHER
2FL: LED DRIVER SUPPLY WIRES SPICED WITHOUT SPLICE BOX. 300.15
RSLV 10/22/2014 10/22/2014 11/17/2014