BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M359479
Premises: 261 WEST 25 STREET MANHATTAN BIN: 1089820     Block: 775   Lot: 5
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 261 W 25 ST Census Tract:   91 Health Area:  5200
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 09/01/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/07/2014 1:39 PM
Application Entered:   10/07/2014 Job Start Date:   10/10/2014
Last Change:   09/01/2017 Job End Date:   10/10/2015
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     08/31/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 011378 Licensee Name: DENNIS J KENNELLY
Firm: 004305 Firm Name: RE-CON ELECTRIC INC
Firm Phone: 718-589-8911  Firm Address: 1090 LEGGETT AVENUE BRONX NY 10474 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $220.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID ASH
Owner Business Name: ROSS ASSOCIATES
Authorized Representative:  DAVID ASH
Relationship To Owner:   PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/07/2014 Notice: C - CALL TO OFFICE 07/19/2016
Power Issued: 10/07/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M359479
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/02/2015 09/03/2015 HMC V G (15) (2) Y
INSPECTION COMMENTS: NONE
 
(2) 04/19/2016 04/19/2016 TUR J X (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR IS SUBMITTING SERVICE IS ADVISORY , NOT COMPLETE
 
(3) 07/18/2016 07/19/2016 TUR J X (30) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS NEED NEW DRAWINGS FOR THIS APP REVISION 2 NOT PROVIDED
 
(4) 08/29/2017 08/29/2017 TOR J Y (34) (0)
INSPECTION COMMENTS: FAIL
 
(5) 08/31/2017 09/01/2017 TOR C R (60) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M359479
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ALL FLOORS)BSMT: SERV.SW AREA. NO GROUND CONDUCTOR TO ELECTRODE FROM S.S
RSLV 09/02/2015 09/02/2015 08/31/2017
 
002 (999) OTHER
(ALL FLOORS)BSMT: FIRE PUMP ROOM.JOCKEY PUMP FEEDERS CONNECTED FROM CONTROLLER695.6(E)
RSLV 09/02/2015 09/02/2015 08/29/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back