| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
4 |
2-400A, 2-600A |
| D. 601 Up to 1200 AMPS |
2 |
1200A, 800A |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
7 |
5-1200A, 2-800A |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
12 |
200A |
| C. 3 Phase Up to 225 AMPS |
5 |
200A |
| D. 3 Phase Over 225 AMPS |
1 |
800A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (FLOOR: 002) SALES OFFICE SCONCES NOT LISTED. |
RSLV |
05/19/2016 |
05/19/2016 |
08/15/2016 |
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 006)APARTMENT PHC & PHA ENTRANCE LIGHT AND RECEPTACLE NOT AFCIPROTECTED. |
RSLV |
05/19/2016 |
05/19/2016 |
08/15/2016 |
| |
| 003 |
(999) |
OTHER (FLOOR: 006)APARTMENT PHC &PHA BALCONY AC HAS NO SERVICE RECEPTACLE. 210.63 |
RSLV |
05/19/2016 |
05/19/2016 |
08/15/2016 |
| |
| 004 |
(999) |
OTHER (FLOOR: 006) AP. PHC FLOOR RECEPTACLE NOT TR. 4-06.11 |
RSLV |
05/19/2016 |
05/19/2016 |
08/15/2016 |
| |
| 005 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS) SMOKE DETECTORS NOT ON AFCI .TOUT |
RSLV |
05/19/2016 |
05/19/2016 |
08/15/2016 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS)NOT ALL KITCHEN COUNTER TOP RECEPTACLES (PLUGMOULD) GFCI PROTECTED.TOUT. 210.8 |
RSLV |
05/19/2016 |
05/19/2016 |
08/15/2016 |
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) LAYOUT IS NOT ACCORDING TO ADVISORY BOARD. |
RSLV |
05/19/2016 |
05/19/2016 |
08/15/2016 |
| |
| 008 |
(999) |
OTHER (ROOF) NO SERVICE SWITCH FOR FANS ON ROOF. 422.30 |
RSLV |
05/19/2016 |
05/19/2016 |
08/15/2016 |