BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M359027
Premises: 335 EAST 13 STREET MANHATTAN BIN: 1006532     Block: 455   Lot: 48
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 335 E 13 ST Census Tract:   40 Health Area:  6200
2 AVENUE & 1 AVENUE Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/25/2014 10:45 AM
Application Entered:   09/25/2014 Job Start Date:   09/25/2014
Last Change:   08/22/2025 Job End Date:   09/25/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   LOFTIN, DANIEL       On     06/05/2025      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010118 Licensee Name: ROBERT MARCHISOTTO
Firm: 002914 Firm Name: R.C.M. ELECTRIC CORP.
Firm Phone: 718-339-2680  Firm Address: 1915 MCDONALD AVE. BLDG REAR BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
Total Fee:  $52.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JASON GLICKI
Owner Business Name: LEMLEE 13TH L.P.
Authorized Representative:  JASON GLICK
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/22/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M359027
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/15/2014 10/22/2014 NRS A (50) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 04/02/2015 04/08/2015 NRS J Y (30) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 01/25/2017 01/26/2017 BMP C R (25) (0)
INSPECTION COMMENTS: OBJECTION REMOVED. CERTIFIED.
 
(4) 06/05/2025 06/06/2025 DLF J (1) (0) Y
INSPECTION COMMENTS: FAIL. INSPECTION INCOMPLETE REQUEST INSPECTION

OBJECTION FOR APPLICATION #: M359027
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASEMENT TO BURNER PANEL DOOR
RSLV 10/15/2014 10/15/2014 04/02/2015
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) BASEMENT
RSLV 10/15/2014 04/02/2015 01/25/2017
 
003 (999) OTHER
BASEMENT SMOKE ALARM FMC NOT SUPPORTED AS 348.30
RSLV 10/15/2014 10/15/2014 04/02/2015
 
004 (999) OTHER
BASEMENT G.R. LUG IN PANEL MOUNTED WITH SHEET METAL SCREW 250.8
RSLV 10/15/2014 10/15/2014 04/02/2015
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASEMENT OIL PUMP
RSLV 10/15/2014 10/15/2014 04/02/2015