BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M358850
Premises: 364 BROADWAY MANHATTAN BIN: 1001862     Block: 172   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 366 BROADWAY Census Tract:   31
N/A Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   FRANKLIN STREET,    WHITE STREET
Status:   C - JOB IS SIGNED OFF 10/04/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   09/22/2014 Job Start Date:   08/11/2014
Last Change:   10/04/2016 Job End Date:   12/11/2014
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     09/30/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 011323 Licensee Name: MICHAEL CASTAGLIOLA, JR.
Firm: 002728 Firm Name: AMC ELEC'L SERVICES, INC.
Firm Phone: 718-965-0809  Firm Address: 140 18TH STREET BROOKLYN NY 11215 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,500.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 39 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52420     Submittal #: 14Q0366  
Owner / Occup:
Owner Business Name: COLLECT POND HOUSES, INC
Authorized Representative:  ANDREW FREIREICH
Relationship To Owner:   REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600AMP
D. 601 Up to 1200 AMPS  1  800AMP
E. Over 1200 AMPS  1  1600AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  #3 AWG, #2 AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 AWG
D. Over 250 MCM  8  600MCM, 500MCM, 350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  MLO 200AMP, 42 CIRCUIT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
Buildings Total                 
Total Units : 8 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 39 #4-Wire 0 #10-Wire 2
Existing Meters 41 + New Meters 0 - Removed Meters 0 = Total Meters 41

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/22/2014 Notice: 1 - FIRST NOTICE 03/28/2016
Power Issued: 09/22/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ACCESS BY APPOINTMENT ONLY. PLEASE CALL 718-965-0809INSTALLING NEW SERVICE TO UPGRADE EXISTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M358850
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/10/2014 12/16/2014 ECH V G (120) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 12/14/2015 12/15/2015 GYM H X (150) (0) Y
INSPECTION COMMENTS: DRAWING NEED TO REV.
 
(3) 03/25/2016 03/28/2016 STP V Y (40) (1)
INSPECTION COMMENTS: FAIL. DID NOT HAVE REVISION #3. NEEDED UPDATED PRINT.
 
(4) 09/30/2016 10/04/2016 BMP C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M358850
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)CELLAR: SERVICE SWITCH #1 DOES NOT CONFIRM TO ADVISORY DRAWINGS110.2 AM
RSLV 12/10/2014 12/10/2014 03/25/2016
 
002 (999) OTHER
(ALL FLOORS)CELLAR: MDP NOT INSTALLED PER ADVISORY DRAWINGS. AM 110.2
RSLV 12/10/2014 12/10/2014 09/30/2016
 
003 (999) OTHER
(ALL FLOORS)CELLAR: EMT FEEDING 200A PANEL NOT SECURELY FASTENED. 358.3(A)
RSLV 12/10/2014 12/10/2014 03/25/2016
 
004 (999) OTHER
(ALL FLOORS)CELLAR: ROOM AND EXIT DOORS DO NOT CONFORM TO ADVISORY DRAWINGSAM 110.2
RSLV 12/10/2014 12/10/2014 03/25/2016
 
005 (999) OTHER
(ALL FLOORS)CELLAR: DP-H DOES NOT CONFORM TO ADVISORY DRAWINGS. AM 110.2
RSLV 12/10/2014 12/10/2014 09/30/2016
 
006 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) BARRIER DOES NOT CONFORM TO DRAWING 110.2 AM
RSLV 03/25/2016 03/25/2016 09/30/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back